| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 72 mm |
| Type | EF 7666 |
| Variant |
| Contact equipping | 1 changeover contact delayed, 1 changeover undelayed |
| Nominal voltage | AC 120 V |
| Time range | 0,2 s - 60 h |
The Dold time relay EF7666.32 is a drop-out delayed industrial time relay for front panel mounting, designed for a rated voltage of AC 120 V at a frequency of 50/60 Hz. It is used for time-delayed control of electrical devices and system components, particularly to account for coast-down behaviour, as occurs with motors or pumps. The time function operates on the principle of drop-out delay with control signal, in accordance with standard EN 61812-1. The device features a wide adjustment range from 0.2 seconds to 60 hours, which can be continuously adjusted front-side via six switchable time ranges. Adjustment is performed using a continuously variable rotary switch with an absolute scale, enabling precise and simple adaptation to different applications.
Applications
This time relay is designed for industrial applications requiring time-delayed switching off. Typical use cases include controlling fans, pumps, lighting systems, or other system components that must continue operating for a certain time after the main signal is switched off. The zero-voltage safety ensures that the relay remains in its output position in the event of a voltage drop, which is important for the safety and stability of control systems.
Functions and Features in Detail
The device provides contact configuration with one delayed changeover contact and one instantaneous changeover contact. The delayed contacts switch only after the set delay time has elapsed, while the instantaneous contacts react immediately when the control signal is applied. The repeatability is ≤ ± 0.5 % of the scale end value, with a permissible deviation of ≤ ± 1 % in the 3 and 6 second ranges. A time progress indicator enables visual monitoring of the timing process. The switching position indicator shows the current state of the contacts, a feature available in the EF 7666 series.
Technology Explained Simply
The timing process is implemented mechanically via a clockwork principle, driven by the energy of the applied voltage. The delay time is selected using a continuously adjustable rotary switch, which influences the speed of the clockwork. Drop-out delay means that the contacts return to their rest position only after the set time has elapsed, once the control signal is removed. The operating time of the contacts is less than 35 ms, and the drop-out time is less than 60 ms. The rated operating voltage is AC 250 V, and the thermal current Ith is 4 A.
Compatibility and Accessories
The time relay is designed for use in industrial control systems and can be combined with other components of the MINITIMER series. The front side is spray water protected and meets protection class IP 65, enabling use in outdoor or damp environments. The width is 72 mm, and the front surface measures 72 x 72 mm, allowing compact mounting in standard control panels. The switching capacity according to AC 15 is 3 A at AC 230 V. The electrical service life is 1 x 10⁵ switching operations at 3 A and 5 x 10⁵ switching operations at 1 A, while the mechanical service life exceeds 30 million switching operations or over 15,000 operating hours.
Mounting and Installation
The device is mounted in front panels, with connection terminals provided for input and output voltage as well as for the control signal. The terminal designations are A1/A2 for operating voltage, B1/B2 for control signal, and 15/16, 27/28 for output contacts. Mounting is done via screw fastening, with terminals designed for cable connections. The reset time is less than 150 ms, enabling rapid reset after switching off.
Advantages in Operation
The combination of wide adjustment range, high repeatability, and mechanical reliability makes this device a robust solution for time-controlled applications. Front-side adjustment and visual indicators simplify commissioning and maintenance. Zero-voltage safety and IP 65 protection class enhance safety and operational reliability in demanding environments. The switching frequency is up to 3000 switching operations per hour, indicating high load capacity in continuously operated systems.