Further information for Dold 0046610 asymmetrical relay BA9040.12/011 3AC50/60Hz 415V
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Measuring range max.
3 AC 690 V
Output contacts
2 C/O contacts
Standard measuring range
3 AC 400 V
Width
45 mm
Type
BA 9040
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 415 V 50/60 Hz
Time delay
0,5 - 5 s
Approvals and Markings
UKCA
Variant
With phase sequence detection. With adjustable time delay
The asymmetry relay BA 9040.12/011 from Dold is an industrial monitoring switch for three-phase networks, detecting voltage asymmetry, phase failure, reverse voltage, and incorrect phase sequence. The device is designed for use in enclosures and serves to ensure operational safety in installations such as elevators, escalators, or crane systems, where correct drive rotation is critical. Monitoring is performed in the standard measurement range of 3 AC 400 V, with the device also capable of operation up to 3 AC 690 V. The rated voltage is 3 AC 415 V at a frequency of 50/60 Hz. The width of 45 mm allows for compact mounting on a DIN rail in accordance with IEC/EN 60715.
Applications
This relay is used in industrial and commercial installations where the reliability of power supply is critical. It protects motors and drives from damage caused by uneven voltage distribution, phase loss, or incorrect rotation direction. Typical applications include conveyor systems, lifting and transport technology, and machines with three-phase drives, where interruption or malfunction can lead to production downtime.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can disconnect the affected drive or the entire system upon detection of a fault. The response delay is adjustable and ranges from 0.5 to 5 seconds, enabling differentiated reaction to short-term disturbances. Phase sequence detection is integrated, allowing early recognition and prevention of incorrect motor rotation. Two LED indicators signal the operating status: a red LED lights up when operating voltage is applied, and a green LED indicates the activated output relay state.
Technology Explained Simply
The relay continuously monitors voltage conditions in a three-phase network. If a deviation from the standardized voltage distribution occurs—such as asymmetry exceeding the set threshold—or if a phase failure is detected, the output contact is activated. The adjustable delay prevents unnecessary shutdowns due to short-term voltage fluctuations. Monitoring is carried out in accordance with IEC/EN 60255-1, the standard for electrical equipment in measurement and monitoring technology. The input voltage range is 0.8 to 1.1 times the rated voltage, ensuring robust operation even under voltage fluctuations.
Compatibility and Accessories
The relay is designed for use in three-phase systems and can operate with various rated voltages, including 3 AC 400 V, 415 V, and 690 V. The terminal connections are rated for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded wire with ferrules according to DIN 46228-1/-2/-3/-4. The terminals are equipped with self-lifting connection washers to ensure secure wire connection. Mounting is done via a DIN rail, which is standard in enclosures.
Mounting and Installation
Installation is performed by securing the device to a DIN rail inside the enclosure. The terminals are designed for easy wiring, with a wire stripping length of 10 mm. The device is rated for an operating temperature up to 60 °C, with copper conductors requiring a temperature class of 60 °C / 75 °C. The tightening torque for the terminals is 0.8 Nm.
Advantages in Operation
Early detection of disturbances in the power network prevents damage to motors and drives. Simple wiring and clear indication via LED displays facilitate commissioning and maintenance. The adjustable response delay allows application-specific adjustment to distinguish between short-term disturbances and actual faults. Operational safety is enhanced by continuous monitoring of phase sequence and voltage conditions, which is particularly beneficial in critical installations. The device is certified with UKCA, confirming compliance with European safety requirements.