| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Time function(s) | Fleeting on make |
| Width | 22,5 mm |
| Type | MK 9989 |
| Variant |
| Contact equipping | 2 contacts fleeting on make (changeover), |
| Nominal voltage | AC/DC 24 V + AC 220 - 240 V |
| Time range | 0,5 - 10 min |
| Variant | 2 fleeting make |
The Dold MK9989 AC/DC24V+AC220-240V 0,5-10M is an
on-delay timer relay for use in industrial control systems. It is designed for time-delayed switching of loads, for example in pumps, motors or lighting, where controlled, step-by-step activation is required. The device is designed for installation in
enclosures and has a width of 22.5 mm, making it suitable for standard DIN rails. The
timing function is achieved via a mechanical wiper, which moves over a defined time range of 0.5 to 10 minutes after the relay is activated. Adjustment is done continuously on an
absolute scale, ensuring precise and repeatable time control. The
repeatability accuracy is less than ±0.5 %, enabling high reliability during repeated operations.
Applications include industrial automation, machine control, systems with sequential processes, and any application where switching delays are necessary to reduce mechanical or electrical stress. The relay is designed for
continuous operation and can be operated in environments with temperatures from -20 °C to +60 °C. Relative humidity may reach up to 93 % at 40 °C, with operating altitude below 2000 m.
Functions and features in detail include two
on-delay wipers (changeover contacts), each functioning as a make and break contact. The contact configuration allows control of two independent loads with time delay. The contacts are made of
AgSnO₂, a material known for high switching capacity and low wear. The
rated voltage is AC/DC 24 V at terminals A3–A2 and AC 220–240 V at terminals A1–A2, enabling use in dual-supply systems. The
rated frequency is 50/60 Hz, with an allowable frequency range of ±5 %. The
release voltage is 15 % of the rated voltage, ensuring secure reset of the relay.
Technology explained simply shows that after applying the operating voltage, the relay moves the wiper over a defined time period until the contact closes. The
reset time is less than 40 ms, ensuring the device is quickly ready for operation again. The
LED indicators signal operational readiness (upper LED) and active contact position (lower LED), facilitating diagnostics during operation. The
switching capacity according to AC 15 is 3 A at AC 230 V for make contacts and 1 A for break contacts, with an electrical life of 500,000 switching cycles at 3 A and AC 230 V. The mechanical life exceeds 30 million switching cycles.
Compatibility and accessories include use with
two-wire initiators, simplifying integration into existing control systems. The device is compliant with
IEC/EN 61812-1 and meets requirements for time relays. The
protection rating is IP 40 for the housing and IP 20 for the terminals, protecting against touch and dust, but not suitable for outdoor use. The
overvoltage category is III, and the insulation test voltage is 2.5 kV. EMC requirements are met according to IEC/EN 61000-4-2 to -4-6, including immunity to fast transients and high-frequency radiation.
Mounting and installation are carried out in standard control panels or enclosures. The device is designed for mounting on 35 mm DIN rails and requires no additional mounting aids. The connection terminals are clearly labeled (A1, A2, A3, 15–18, 21–24), ensuring unambiguous assignment of wires. The
short-circuit resistance is ensured by a maximum fuse rating of 6 A gG/gL.
Operational advantages include high repeatability accuracy, simple adjustment on the absolute scale, and clear signaling via LED indicators. The combination of two wipers enables control of multiple loads with individual time delays. The device is designed for industrial environments and meets requirements for reliability and longevity.