| Technical data |
| 1- / 3-phase | 3 |
| Enclosure design | Distribution board |
| Measuring range max. | 690 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 380 - 415 V |
| Width | 70 mm |
| Type | IP 9075 |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC 480 - 550 V 50 - 400 Hz |
| Variant | Energized / De-energized on trip programmable. Manual reset programmable |
The Dold fuse monitor type IP9075.12/010 AC50...400HZ 480-550V is an industrial monitoring device of the VARIMETER series, designed for continuous monitoring of up to three load fuses in three-phase networks. The device detects the failure of one or more fuses, even if the connected consumers are switched off, and signals this condition via output contacts. This increases the operational safety of plants and ensures availability through preventive maintenance. The application is in industrial and installation distributors, where early detection of fuse failures can prevent costly damage.
Applications
The fuse monitor is designed for use in three-phase networks with a rated voltage of AC 480 to 550 V and a frequency of 50 to 400 Hz. It monitors load fuses in plants, for example those operating three-phase motors, and can be used for automatic switching off or blocking switching on in case of fuse failure. The maximum measurement voltage is 690 V, with the standard measurement range at 3 AC 380 to 415 V. The device is suitable for all common fuse types and sizes and operates independently of the direction of the network current.
Functions and equipment in detail
The device features two changeover contacts as output contacts, which are either activated (operating current principle) or deactivated (resting current principle) depending on the programming. This setting is programmable via the programming terminals X3, X4, and X5. Additionally, the memory behavior can be configured via terminals X1 and X2, where a bridge between X1 and X2 enables automatic reset. Indication is provided via two LEDs: a green LED indicates intact fuses, while a red LED indicates a fuse failure.
Technology explained simply
The measurement paths of the fuse monitor have an internal resistance in the megohm range, ensuring compliance with regulations for touch voltage (internal resistance > 2000 Ohm/V). This is particularly important when a fuse is missing or defective. The cable length for the programming terminals X3, X4, and X5 must not exceed 3 m to ensure reliable signal transmission. The devices are specified according to IEC/EN 60255-1, ensuring compliance with standards for electrical measuring instruments and installations.
Compatibility and accessories
The device is manufactured in I form factor, with a width of 70 mm and a depth of 59 mm. The connection terminals are arranged at the bottom, enabling installation in installation and industrial distributors according to DIN 43880. It is compatible with various fuse types and sizes and can operate reliably in three-phase networks with asymmetric voltage or harmonic distortion, as well as with regenerative motors. The response time is shorter than that of motor protection switches, enabling faster reaction to fault conditions.
Mounting and installation
Mounting is carried out in standard installation distributors or industrial distributors, with the width of 70 mm and depth of 59 mm defining the installation requirements. The terminals are designed for direct connection to the lines before and after the fuses (L1, L2, L3 and L1’, L2’, L3’). The programming terminals X1 to X5 allow individual configuration of the operating mode. De-energizing the device requires switching off the upstream main switch.
Advantages in operation
Early detection of fuse failures, even with switched-off consumers, increases operational safety. Preventive maintenance enables avoidance of damage that could result from undetected failures. Programmable functions such as operating current/resting current principle and memory behavior offer flexibility when integrating into existing plants. The clear LED indication facilitates diagnosis and maintenance. Reliability in asymmetric networks and with regenerative motors makes the device suitable for demanding industrial environments.