| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 2 C/O contacts |
| Time function(s) | Fleeting on make |
| Width | 22,5 mm |
| Type | MK 9989 |
| Variant |
| Contact equipping | 2 contacts fleeting on make (changeover), |
| Nominal voltage | AC/DC 24 V + AC 220 - 240 V |
| Time range | 0,15 - 3 s |
| Variant | 2 fleeting make |
The Dold MK9989 AC/DC24V+AC220-240V 0,15-3S is an
on-delay toggle relay for use in industrial control systems. It is designed for time-controlled switching of loads, with contacts switching within a defined time range of 0.15 to 3 seconds after applying the operating voltage. The device is designed for installation in
enclosures and has a width of 22.5 mm, making it suitable for standard control panels. The
dual-voltage version allows operation via two different voltage levels: AC/DC 24 V and AC 220–240 V, enabling flexible use in various networks.
Applications include control of motors, lighting, heating systems, or other electrical loads where a time-delayed switching function is required. Typical uses are found in manufacturing automation, building automation, or machine control, where precise, repeatable time delay is necessary. The relay is compliant with
IEC/EN 61812-1 and meets safety and reliability requirements for industrial environments.
Functions and equipment in detail include two
on-delay toggle switches (changeover contacts), each functioning as a make and break contact. The time delay is continuously adjustable on an
absolute scale, ensuring high accuracy in setting. The
repeatability accuracy is less than ±0.5 % of the scale end value, ensuring high precision in repeated switching operations. Two
LED indicators signal the operating status: the upper LED lights up when operating voltage is applied, and the lower LED indicates when the output relay is active (contacts 15–18 closed). The device is
operable with two-wire initiators, simplifying integration into existing control systems.
Technology explained simply is based on an electromechanical relay principle, where contacts switch after voltage application via a mechanical toggle action. The time delay is achieved by an integrated timing mechanism that sets the switching time within the specified range of 0.15 to 3 seconds. The
drop-out voltage is 15 % of the rated voltage, meaning the relay reliably resets even with slight voltage fluctuations. The
rated power consumption is 8.5 VA (AC 230 V) and 1 W (DC 24 V), ensuring efficient power usage. The
reset time is less than 40 ms, making the device quickly available for the next switching operation.
Compatibility and accessories include use with two-wire initiators, suitable for operating sensors or other control elements. The device is available in a
dual-voltage version, allowing operation on both 24 V and 230 V mains voltages. It is also available in a variant with an
instantaneous contact (model MK 9989.77), which includes an additional non-delayed changeover contact. The
switching capacity according to AC 15 is 3 A / AC 230 V for make contacts and 1 A / AC 230 V for break contacts, sufficient for controlling medium loads.
Mounting and installation is done in standard control panels with a width of 22.5 mm. The terminals are designed for secure connections, and the
protection rating of the housing is IP 40, while the terminals have IP 20. The housing is made of
thermoplastic with V0 behavior according to UL Subject 94, ensuring a high flame retardancy class. The
temperature ranges for operation are between -20 °C and +60 °C, and for storage between -25 °C and +70 °C. The
relative humidity may reach up to 93 % at 40 °C. The maximum operating altitude is 2000 m above sea level.
Operational advantages include high repeatability accuracy, easy adjustment on the absolute scale, and clear indication via LED indicators. The mechanical life exceeds 30 million switching operations, ensuring high reliability over long periods. The electrical life is at least 500,000 switching operations at 3 A and AC 230 V. The
permissible switching frequency is 6000 switching operations per hour, suitable for intensive operating conditions.
Short-circuit resistance is ensured by a maximum fuse rating of 6 A gG/gL. EMC requirements are met, including immunity to electrostatic discharge, high-frequency radiation, and fast transients.
The device is designed for
continuous operation and meets requirements for
overvoltage category III. The insulation test voltage is 2.5 kV for a duration of 1 minute. The
rated impulse withstand voltage is 4 kV at pollution degree 2.
Radio interference suppression complies with Class B limits according to EN 55011.
Vibration resistance is tested according to IEC/EN 60068-2-6 with an amplitude of 0.35 mm and a frequency of 10 to 55 Hz.
Climate resistance conforms to standard 20/060/0.
Key terms in the text:
on-delay toggle relay,
dual-voltage version,
absolute scale,
repeatability accuracy,
IP 40,
IEC/EN 61812-1.