Dold 0044504, EAN: 4030641445041

Dold 0044504 MK9151.11 2-450K-OHM AC110-127V level relay

Dold 0044504 MK9151.11 2-450K-OHM AC110-127V level relay

Lieske Part No. 1001937
Mfg Part No 0044504
EAN-Code 4030641445041
Manufacturer Dold
Here only 164,26 EUR
195,47 EUR incl. VAT

Further information for Dold 0044504 MK9151.11 2-450K-OHM AC110-127V level relay

Technical data
ClassificationFüllstandsüberwachung
Enclosure designSwitch cabinet
Measuring range max.450 kΩ
Output contacts1 C/O contact
Width22,5 mm
TypeMK 9151
Operate delayYes
Variant
Auxiliary voltageAC 110 - 127 V
Contact equipping1 changeover contact
Response value2 - 450 kOhm
VariantTime delay, when level rises over and drops under setting value
The Dold level relay MK9151.11 is an industrial fill-level monitoring controller for conductive liquids and powders. It is used for continuous monitoring and control of fill levels, for example to prevent overfilling or dry running in tanks. The device is designed for use in enclosures and has a width of 22.5 mm, making it suitable for standard control panels. The MK9151.11 variant is designed for an auxiliary voltage range of AC 110–127 V and offers a response value range of 2 to 450 kOhm, enabling differentiation between liquid and foam. The time delay when exceeding or falling below the set level allows for stable and disturbance-resistant operation.

Applications
This relay is used in fill-level monitoring systems, particularly in process industries, food processing, or water treatment. It is suitable for 1-point and 2-point level control, with 1-point control intended for overfill or dry-run protection in free inflow or outflow conditions. In 2-point control, the liquid level is maintained between a minimum and maximum level, with electrodes MIN, MAX and COM connected. Applications range from monitoring maximum and minimum fill levels to regulating the mixing ratios of conductive liquids. The device is also suitable for general resistance monitoring tasks, such as detecting limit temperatures using PTC resistors.

Functions and Equipment in Detail
The device features three electrode terminals for 1-point and 2-point level control. The reference electrode (COM) is typically mounted at the lowest point of the tank. In conductive tanks, the tank itself can serve as the reference electrode. Measurement is performed via a galvanically isolated measurement circuit, providing high interference immunity. The response and reset delay is adjustable from 0.2 to 20 seconds, allowing adaptation to different process conditions. The output contacts consist of a changeover contact, used for switching operations in control systems. Programming is done for either the operating current principle (without bridge, output relay activated in fault condition) or the resting current principle (bridge X1-X2 or X1-COM, output relay not activated in fault condition).

Technology Explained Simply
The measurement circuit generates an alternating current that flows through the electrodes in the tank. The resistance of the liquid is measured and compared with the set response value. If the value is exceeded or undershot, the output relay switches after the set delay time. The maximum cable length to the electrodes is 3000 meters, with the actual length depending on the set resistance range. For a measurement range of 2 to 450 kOhm, the maximum cable length is 3000 meters at 5 kOhm. The maximum measurement voltage is approximately AC 10 V, and the maximum measurement current is approximately AC 1.5 mA. The operating voltage is in the range of AC 110–127 V, with a nominal power of approximately 2 VA. The frequency range coverage is between 45 and 400 Hz.

Compatibility and Accessories
The relay is suitable for use with standard market-available electrodes. The connection terminals are designed for connecting the electrodes (MIN, MAX, COM), control input (X1), control output (X2), and changeover contacts (11, 12, 14). Device indicators include a green LED for operational readiness and a yellow LED for contact status. The devices are specified according to IEC/EN 60255-1 and can optionally be equipped with a tamper-proof transparent cover or safe isolation according to IEC/EN 61140 and IEC/EN 60947-1. The output contacts are rated for a thermal current of 5 A, with switching capacity of 3 A/AC 230 V for the NO contact and 1 A/AC 230 V for the NC contact. The electrical life expectancy is approximately 500,000 switching cycles at 1 A/AC 230 V, and the mechanical life expectancy is 30 million switching cycles. The maximum short-circuit current rating is 4 A gG/gL.

Mounting and Installation
The device is installed in an enclosure and connected via the designated terminals to the electrodes and auxiliary voltage. The electrodes must be positioned in the tank according to the desired control mode (1-point or 2-point). The reference electrode (COM) is mounted at the lowest point. The response value is set using a logarithmically scaled dial. The delay time is also adjusted via a scale. The device indicators (LEDs) provide visual monitoring of the operating status. The maximum operating frequency is 6000 switching cycles per hour.

Advantages in Operation
The relay offers high interference immunity due to the galvanically isolated measurement circuit, making it suitable for industrial environments with electromagnetic interference. The wide adjustment range of 2 to 450 kOhm enables precise differentiation between liquid and foam. The adjustable delay time prevents false switching due to short-term level fluctuations. The clear LED indication simplifies diagnostics during operation. Compatibility with standard electrodes and the high contact life ensure flexible and reliable integration into existing systems. The maximum cable length of 3000 meters allows flexible electrode placement in the tank, even for large volumes.

Fill-level monitoring
Level relay
Galvanically isolated measurement circuit
Response delay
Changeover contact
IEC/EN 60255-1