Further information for Dold 0044331 undervoltage relay 0.5-10S
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N 400/690 V
Time delay
0,5 - 10 s
Approvals and Markings
UKCA
Variant
For 3p4w systems. With adjustable time delay
The under-voltage relay BA9043/002 from Dold is a 3-phase monitoring device for three-phase networks with neutral conductor. It is designed for continuous monitoring of the supply voltage and disconnects output contacts in case of under-voltage to protect connected devices or systems from damage. The device is rated for nominal voltages of 3/N AC 400/690 V and operates in the frequency range of 50 to 400 Hz. Measurement is performed via arithmetic mean calculation of the three phases against the neutral conductor, ensuring precise and reliable voltage monitoring. Device settings are adjusted via rotary potentiometers on the front panel, allowing continuous adjustment of pickup and dropout values between 0.85 and 1.05 of nominal voltage, as well as a dropout ratio (hysteresis) between 0.75 and 0.95 of the pickup value.
Applications
This relay is suitable for industrial applications and railway applications where reliable voltage monitoring is required. It is mounted in enclosures and designed for continuous operation. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The maximum operating altitude is 2000 m above sea level.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, rated for switching operations in AC 15 service. The switching capacity is 2 A at AC 230 V for make contacts and 1 A at AC 230 V for break contacts. The electrical life expectancy is 2 x 10⁵ switching operations at 3 A and AC 230 V. The mechanical life expectancy exceeds 30 x 10⁶ switching operations. The contacts are rated for a thermal current of up to 6 A per contact. Short-circuit resistance is ensured by a maximum fuse rating of 4 A gG/gL.
Technology Explained Simply
The relay operates on the principle of rest current, meaning the output relay remains inactive in the event of a fault and stays in its resting position. This prevents unwanted switching operations. The time delay is adjustable and ranges from 0.5 to 10 seconds. However, this delay is only effective if the voltage is at least 60 % of the nominal voltage. Below 40 % of nominal voltage, the output relay drops out immediately. Adjustment is performed via rotary potentiometers on the front panel, enabling user-friendly and precise tuning. LED indicators signal operational readiness (red LED) and contact position (green LED). The device is insensitive to harmonics, meaning it operates reliably even with supply voltages containing harmonic distortions.
Compatibility and Accessories
The relay is designed for networks with or without neutral conductor, with the BA9043/002 variant specifically intended for systems with neutral conductor. It is compliant with IEC/EN 60255-1 and bears the UKCA mark. Mounting is performed on a DIN rail according to IEC/EN 60715. The width is 45 mm, enabling compact installation in standard enclosures. The terminals are designed for 2 x 2.5 mm² single- or multi-strand conductors, with a stripping length of 10 mm and a tightening torque of 0.8 Nm.
Mounting and Installation
Installation is carried out by mounting on a DIN rail inside the enclosure. The connection terminals are intended for connection to phases L1, L2, L3 and the neutral conductor N. The output contacts (11, 12, 14 and 21, 22, 24) are connected according to the circuit diagram. Adjustment of pickup and dropout values as well as time delay is performed via the rotary potentiometers on the front panel. The devices are designed for use in industrial environments and feature high EMC immunity, including protection against static discharges (8 kV), HF radiation (20 V/m), and fast transients (2 kV).
Advantages in Operation
Continuous monitoring of supply voltage enables preventive maintenance and contributes to higher productivity. Quick fault localization via LED indicators and clear signaling of contact position simplifies troubleshooting. Harmonic insensitivity and high EMC immunity ensure reliable operation even in electrically demanding environments. Simple operation and compact design make the device a practical solution for voltage monitoring in industrial systems.