Further information for Dold 0044056 BA9040.12/010 3AC50/60Hz 400V 0.5-5S asymmetrical relay
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Measuring range max.
3 AC 690 V
Output contacts
2 C/O contacts
Standard measuring range
3 AC 400 V
Width
45 mm
Type
BA 9040
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 400 V 50/60 Hz
Time delay
0,5 - 5 s
Approvals and Markings
UKCA, CCC
Variant
Without phase sequence detection. With adjustable time delay
The asymmetry relay BA9040.12/010 from the VARIMETER series by Dold monitors three-phase networks for voltage asymmetry, phase failure, reverse voltage, and incorrect phase sequence. It is designed for use in industrial applications such as elevators, escalators, or crane systems, where reliable power supply and correct rotation direction of drives are critical. The device detects potential network disturbances early to avoid costly damage and enhance operational safety. The version with adjustable time delay allows application-specific adjustment of the response time, preventing unwanted shutdowns during short-term voltage fluctuations.
Applications
This relay is intended for use in industrial enclosures and is particularly suitable for systems requiring continuous and stable power supply. It monitors three-phase AC networks with a rated voltage of 3 AC 400 V at 50/60 Hz. The maximum measuring voltage is 3 AC 690 V, making it usable in networks with higher voltage, provided the rated voltage remains within the standard range. Monitoring is carried out in accordance with IEC/EN 60255-1, ensuring compliance with international standards for electrical measuring instruments.
Functions and Features in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits or warning signals. The response delay is adjustable between 0.5 and 5 seconds, enabling flexible adaptation to different requirements. The contacts are rated for a switching current of 3 A at 230 V AC, sufficient for typical control and signaling applications. Two LED indicators display the operating status: a red LED lights up when operating voltage is applied, and a green LED indicates the activated state of the output relay. This visual feedback simplifies commissioning and maintenance.
Technology Explained Simply
The relay monitors voltage in all three phases (L1, L2, L3) and detects deviations from symmetrical voltage distribution. Upon detection of asymmetry, phase failure, or reverse voltage, the output contact is switched accordingly. The time delay prevents false alarms during short-term voltage fluctuations. The width of the device is 45 mm, allowing compact mounting on a DIN rail in accordance with IEC/EN 60715. The connection terminals are designed for conductor cross-sections of 2 x 1.5 mm² stranded wire with ferrule or 2 x 2.5 mm² solid wire, with a tightening torque of 0.8 Nm. The terminal connections comply with IEC/EN 60999-1.
Compatibility and Accessories
The relay is designed for use in three-phase networks and meets the requirements of IEC/EN 60255-1. It is certified with UKCA and CCC, enabling use in corresponding markets. The BA9040.12/010 variant is configured without phase sequence detection, making it suitable for applications where drive rotation direction does not need to be monitored. Mounting is on a DIN rail, with device dimensions of 45 mm (width) × 74 mm (height) × 133 mm (depth).
Mounting and Installation
Mounting is on a DIN rail within the enclosure. The connection terminals are designed for copper conductors, with maximum cross-sections of 2.5 mm² for solid conductors and 1.5 mm² for stranded wire. The stripping length for conductors is 10 mm. The tightening torque for terminals is 0.8 Nm. Wiring is done via terminals L1, L2, L3 for network voltage and contacts 11, 12, 14 and 21, 22, 24 for output signals. Terminal designations are detailed in the datasheet.
Operational Advantages
Early detection of network disturbances enables the relay to protect connected machines and systems from damage. Simple wiring and clear LED indication facilitate commissioning and maintenance. The adjustable time delay allows adaptation to specific requirements, increasing system reliability. The 45 mm width and DIN rail mounting ensure compact integration into existing enclosures. Compliance with IEC/EN 60255-1 ensures the quality and reliability of the device.