| Technical data |
| 1- / 3-phase | 3 |
| Enclosure design | Distribution board |
| Measuring range max. | 690 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 380 - 415 V |
| Width | 70 mm |
| Type | IP 9075 |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC 380 - 440 V 50 - 400 Hz |
| Variant | Energized / De-energized on trip programmable. Automatic reset |
The Dold fuse monitor IP9075.12 AC50...400HZ 380-440V is an industrial monitoring switch of the VARIMETER series, designed to monitor up to three load fuses in three-phase networks. The device enables early detection of blown fuses, even when connected consumers are switched off, to prevent operational interruptions and damage to installations. It is designed for use in installation and industrial distribution boxes and complies with the standard IEC/EN 60255-1.
Applications
This fuse monitor is suitable for monitoring load fuses in three-phase installations up to 3 AC 690 V. It is particularly used in systems where availability and operational safety are critical, such as automatic disconnection or lockout of three-phase motors in case of failure of one or more phase fuses. The application is independent of rotation direction and functions even in unbalanced or harmonic-loaded networks, as well as with regenerative motors.
Functions and Equipment in Detail
The device reliably detects fuse failures and features two changeover contacts as output contacts. The operating mode is programmable: it can be operated in the current-on principle (output relay activated in case of fault) or in the current-off principle (output relay deactivated in case of fault). This setting is made via terminals X3-X4 or X4-X5. The device is designed without memory function, meaning it returns to normal state after a fault condition without requiring an external reset action. Indication is provided by two LEDs: a green LED indicates intact fuses, while a red LED signals a fuse failure.
Technology Explained Simply
The fuse monitor monitors voltage before and after the load fuses (terminals L1, L2, L3 and L1', L2', L3'). The internal resistance of the measurement paths is in the megohm range (over 2000 Ohm/V), ensuring compliance with touch voltage regulations, even if a fuse is missing or defective. The rated voltage is AC 380–440 V at a frequency of 50–400 Hz. The standard measurement range is 3 AC 380–415 V, with a maximum measurement range up to 690 V. Programming of the operating mode is done via terminals X3–X5, with the maximum cable length between these terminals being 3 m.
Compatibility and Accessories
The device is suitable for all common fuse types and sizes. It is designed in I form factor, with a width of 70 mm and a depth of 59 mm. The connection terminals are located at the bottom and are designed for installation and industrial distribution boxes according to DIN 43880. The IP 9075.12 variant provides two changeover contacts as output contacts, enabling flexible integration into existing control systems.
Mounting and Installation
Mounting is done in standard installation distribution boxes. The terminals are arranged at the bottom, enabling easy wiring. The width of 70 mm corresponds to the standard width for devices in this group. The connection terminals are designed for connection with cables, with the programming terminals X3–X5 not exceeding a maximum cable length of 3 m.
Operational Advantages
Early detection of fuse failures increases system availability and prevents costly damage. The short response time compared to motor protection switches enables rapid reaction to faults. The rotation-direction-independent function and tolerance to unbalanced or harmonic-loaded networks increase reliability in complex installations. The clear LED indication simplifies diagnosis and maintenance.
Enclosure Form and Width
The device is designed as an installation distributor with a width of 70 mm. The form factor is designed for use in distribution boxes according to DIN 43880, with connection terminals located at the bottom. The depth is 59 mm, enabling compact mounting in standard distribution boxes.
Programmable Functions
The operating mode (current-on or current-off principle) is programmable via terminals X3–X5. The device is designed without memory function, meaning it automatically resets after a fault condition without requiring an external reset signal. Indication is provided by two LEDs, which visually signal the status of the fuses.
Application Safety
The fuse monitor is designed for use in industrial installations where system reliability and availability are critical. The construction ensures safe and reliable monitoring even under difficult operating conditions, including unbalanced networks and regenerative motors. Compliance with the standard IEC/EN 60255-1 ensures conformity with applicable safety standards.