| Technical data |
| 1- / 3-phase | 3 |
| Enclosure design | Distribution board |
| Measuring range max. | 690 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 380 - 415 V |
| Width | 70 mm |
| Type | IP 9075 |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC 480 - 550 V 50 - 400 Hz |
| Variant | Energized / De-energized on trip programmable. Automatic reset |
The fuse monitor IP9075.12 from Dold is an industrial monitoring switch for continuous monitoring of up to three load fuses in three-phase networks. The device is specifically designed for use in installation and industrial distribution systems and monitors the integrity of the fuses, even when the connected consumers are switched off. Early detection of blown fuses enables preventive maintenance measures and thus prevents costly damage during operation. The operational safety and high availability of the system are thereby increased.
Applications
The fuse monitor IP9075.12 is intended for use in industrial and commercial installations, particularly in systems with three-phase motors, where disconnection or lockout is required in case of failure of one or more phase fuses. It is suitable for installations operating at a nominal voltage of AC 480 to 550 V and a frequency of 50 to 400 Hz. The maximum measuring voltage is 690 V, with the standard measuring range designed for 3 AC 380 to 415 V. The device is rotationally independent and can therefore be used regardless of the phase sequence in the network.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary functions such as disconnection or warning signals. The operating mode can be programmed between the operating current principle (output relay is activated in case of fault) and the resting current principle (output relay remains deactivated in case of fault). This setting is made via the programming terminals X3, X4, and X5. The device is designed without memory function, meaning that the fault condition is not stored after a reset. Indication is provided by two LEDs: a green LED indicates intact fuses, while a red LED indicates a fuse failure.
Technology Explained Simply
The fuse monitor monitors the voltage before and after the fuses. In the event of a fuse failure, the voltage drop is detected, and the device responds according to the programmed logic. The internal resistance of the measuring paths is in the megohm range, ensuring compliance with regulations for touch voltage (internal resistance > 2000 Ohm/V), even if a fuse is missing or defective. The cable length for programming terminals X3, X4, and X5 must not exceed 3 m to ensure reliable signal transmission.
Compatibility and Accessories
The device is suitable for all common fuse types and sizes and can be used in three-phase networks up to 3 AC 690 V. It is compliant with IEC/EN 60255-1 and can be used in combination with other devices from the VARIMETER series (such as IL 9075, SL 9075, SP 9075). The housing design is intended for installation distributors, with a width of 70 mm and bottom-mounted terminals, in accordance with DIN 43880.
Mounting and Installation
Mounting is carried out in standard installation distributors or industrial distributors. The terminals are located at the bottom, enabling easy integration into existing control systems. The devices are suitable for use in enclosures with mounting plates and cable ducts. The connection terminals are designed for connection to the network lines (L1, L2, L3 before the fuses and L1', L2', L3' after the fuses).
Operational Advantages
Early detection of fuse failures, even when consumers are switched off, enables quick response and prevents unexpected outages. The reliability of detection remains intact even in asymmetric networks, harmonic loads, or back-feeding motors. The shorter response time compared to motor protection switches increases the system's reaction speed. The clear LED indication simplifies diagnosis and maintenance.
Housing Design and Width
The device is designed in I-type housing, with a width of 70 mm and a depth of 59 mm. The housing design is intended for installation distributors, with terminals located at the bottom. The construction meets the requirements for industrial switching devices and is suitable for use in enclosures.
Compliance with Standards
The device complies with the standard IEC/EN 60255-1, which applies to electrical equipment in measurement and monitoring technology. Compliance ensures reliability and safety in industrial applications.
Programmable Functions
The functions of the device are programmable via terminals X1, X2, X3, X4, and X5. The selection between operating current and resting current principle, as well as the setting of memory behavior, is made via the corresponding bridge connections. The programming terminals allow flexible adaptation to the specific requirements of the installation.
Indication and Diagnosis
Two LEDs provide visual indication of the operating status: the green LED indicates that all monitored fuses are intact, while the red LED signals a failure. This indication facilitates quick identification of faults and reduces maintenance time.
Use in Three-Phase Networks
The device is specifically designed for three-phase networks and can monitor up to three phase fuses. Monitoring is independent of the network rotation direction, enabling flexible installation. The maximum voltage is 690 V, with the standard range designed for 380 to 415 V.
Reliability and Maintenance
The reliability of detection is ensured by the high internal resistance values of the measuring paths. Preventive maintenance is supported by early notification of fuse failures, which increases operational safety. Simple mounting and clear indication facilitate maintenance and reduce downtime.
Industrial Applications
The fuse monitor IP9075.12 is used in industrial installations where the reliability of power supply is critical. It is particularly suitable for motors protected by fuses and enables automatic disconnection or lockout in case of fuse failure. Integration into existing control systems is easy due to the standard width and DIN-compliant mounting.
Functions in Detail
- Monitoring of up to three load fuses
- Programmable selection between operating current and resting current principle
- No memory function (automatic reset)
- Two changeover contacts as output contacts
- LED indication: green for intact fuses, red for failure
- Max. measuring voltage: 690 V, standard range: 3 AC 380–415 V
- Nominal voltage: AC 480–550 V, 50–400 Hz
- Housing design: installation distributor, width 70 mm
- Programming via terminals X1–X5
- Cable length for programming terminals max. 3 m
- Internal resistance of measuring paths in the MOhm range
- Compliant with IEC/EN 60255-1
- Rotationally independent
- Shorter response time than motor protection switches
- Suitable for all fuse types and sizes
- Use in three-phase networks up to 3 AC 690 V
- Mounting in installation distributors according to DIN 43880
- Terminals located at the bottom
- Settings via bridge connections at X1–X5
Application Scenarios
The device is used in industrial installations where the reliability of power supply is critical. Examples include monitoring of three-phase motors protected by fuses, as well as in installations requiring automatic disconnection or lockout in case of fuse failure. Integration into existing control systems is easy due to the standard width and DIN-compliant mounting.
Reliability and Safety
The reliability of detection is ensured by the high internal resistance values of the measuring paths. Preventive maintenance is supported by early notification of fuse failures, which increases operational safety. Simple mounting and clear indication facilitate maintenance and reduce downtime.
Conclusion
The fuse monitor IP9075.12 from Dold is a reliable and flexible device for monitoring load fuses in three-phase networks. With programmable functions, clear LED indication, and robust construction, it offers high operational safety and availability. Compliance with IEC/EN 60255-1 and suitability for industrial applications make it an appropriate device for use in enclosures and installation distributors. Integration into existing installations is simple and requires no additional components.