Further information for Dold 0043771 BA9036 AC50HZ 100V voltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
AC 100 V 50 Hz
Time delay
without
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation
The Dold voltage relay BA9036 AC50HZ 100V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of the supply voltage to detect voltage dips or failures early, thereby increasing the operational safety of electrical installations. The device setting is performed via rotary switches on the front, ensuring simple and user-friendly configuration. The relay operates on the standby current principle, where the contacts are closed during normal operation and open in case of undervoltage.
Applications
This relay is suitable for use in industrial and technical installations where reliable voltage monitoring is required. Typical application areas include monitoring of supply networks in machine controls, drive technology, pump and fan systems, as well as in safety and emergency power systems. The ability to monitor both DC and AC voltage expands its range of applications. The adjustable pickup and dropout values allow application-specific adaptation to detect only relevant voltage fluctuations and avoid unnecessary tripping.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary relays, signal indicator lights, or switching devices. The pickup delay is adjustable and ranges from 0.5 to 10 seconds, allowing short-term voltage dips to be ignored to prevent false tripping. The LED indicators signal operational readiness (upper LED) and activated contact position (lower LED), facilitating diagnosis during operation. The rated voltage is AC 100 V at 50 Hz, with the device designed for voltage ranges from 24 to 400 V. The maximum rated voltage is AC 400 V.
Technology Explained Simply
The relay operates without auxiliary voltage, meaning it is connected directly to the voltage source to be monitored. The setting is done via rotary controls that define the pickup value (e.g., 90 % of rated voltage) and the dropout value (hysteresis). The hysteresis is 0.75 to 0.95 of the set pickup value to prevent chattering of contacts during voltage fluctuations near the threshold. The temperature influence is less than 0.05 % per Kelvin, ensuring stable operation even with temperature variations during use. The overload capacity is 1.2 times the rated voltage continuously, providing some tolerance for short-term voltage surges.
Compatibility and Accessories
The relay is designed for use in enclosures and has a mounting width of 45 mm, making it integrable into standard control panels. For DC voltages above 60 V, an external series resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. The required resistors are available as accessories, e.g., ZWS 20 SL 1.5 kΩ 20 W for DC 110 V. The devices comply with IEC/EN 60255-1 and carry the CCC certification.
Mounting and Installation
Mounting is done in standard control panels or enclosures. The terminals are designed for direct connection to wires. When using an external series resistor, sufficient distance to adjacent components must be maintained, as the resistor becomes very hot during operation. The connection terminals are clearly labeled to ensure correct wiring.
Operational Advantages
By detecting voltage anomalies early, the relay enables preventive maintenance, avoiding failures and downtime. Quick fault localization via LED indicators and adjustable thresholds increases operational safety. The high mechanical life of 30 million switching operations and electrical life of 150,000 switching operations at 6 A/AC 230 V ensure long service life. The switching capacity according to AC 15 (2 A/AC 230 V) and DC 13 (1 A/DC 24 V) is sufficient for typical control tasks. The short-circuit withstand is secured with a maximum fuse rating of 4 A gG/gL.