| Technical data |
| Enclosure design | Distribution board |
| Output contacts | 2 C/O contacts |
| Time function(s) | On-delay |
| Width | 17,5 mm |
| Type | IK 7825 |
| Variant |
| Contact equipping | 1 changeover contact delayed |
| Nominal voltage | DC 24 V |
| Time range | 0,5 - 10 min |
The Dold time relay IK7825.81 DC24V 0,5-10M is a delayed-on time relay for industrial control applications. It is used for time-controlled activation of switching operations, where the output contact switches only after a set delay time. The device is designed for use in installation distributors and has a width of 17.5 mm, making it suitable for standard switchboards. The rated voltage is DC 24 V, and the delay time can be adjusted continuously in the range of 0.5 to 10 minutes. The time function is delayed-on, meaning the contact switches only after the set time has elapsed once the input voltage is applied.
Applications
This relay is suitable for applications requiring a time-delayed switching function, for example in automation technology, pump control, lighting systems, or drive control. The repeat accuracy of ≤ 0.5 % + 10 ms ensures high precision in repeated switching operations. The tolerance of the end value is -5 % to +25 % of the nominal value, which should be considered when planning the switching time.
Functions and Equipment in Detail
The device features a changeover contact that switches with delay. The contact rating is designed for a thermal current load of 16 A. The contacts are made of AgSnO₂, a material known for its high switching durability and low wear. An integrated push-button allows manual actuation of the contact and also serves as a switching position indicator. The indicator shows whether the relay is energized by the push-button being depressed.
Technology Explained Simply
The time delay is adjusted continuously via a relative scale, with the scale range being 1:20. The reset time is approximately 60 ms after the delay time has elapsed and approximately 700 ms during the time interval. The voltage influence is less than 1 % over the voltage range of 90 to 110 % of the rated voltage. The temperature dependence is less than 0.1 % per Kelvin, enabling stable operation under varying environmental conditions. The electrical life is up to 150 x 10⁴ switching operations at 6 A with ohmic load and 500 switching operations per hour, with a maximum switching frequency of 1000 switching operations per hour.
Compatibility and Accessories
The relay is designed for use in switchboards with standard width. It is compatible with a connection cross-section of up to 2.5 mm² for solid conductors according to DIN 46228-1/-2/-3/-4. Terminal marking follows EN 50005. The arc limit curve indicates the maximum switching voltages and currents at which safe switching without sustained arc is guaranteed. The short-circuit resistance is defined by a maximum fuse rating of 16 A gG / gL according to IEC/EN 60947-5-1.
Mounting and Installation
The device is intended for installation in installation distributors. Mounting is carried out in standard switchboards with a width of 17.5 mm. The terminals are designed for connection with conductors according to DIN 46228. The operating temperature range is from -20 °C to +45 °C, and the storage temperature range is from -25 °C to +70 °C. The relative humidity is up to 95 % at 40 °C. The operating altitude is limited to ≤ 2000 m.
Advantages in Operation
The relay offers high switching durability with a mechanical life of over 3 x 10⁶ switching operations. EMC tests according to IEC/EN 61000-4-2 to -4-6 ensure good resistance to electromagnetic interference. The enclosure protection rating is IP 40, and the terminals are IP 20, providing protection against contact and dust, but not against water. The insulation test is performed at 2.5 kV for 1 minute. The overvoltage category is III, which is typical for industrial applications. Radio frequency interference suppression complies with emission limit class B according to EN 55011.
Approvals and Markings
The device complies with standard EN 61812-1 for delayed-on time relays. Approvals include EMC tests according to IEC/EN 61000-4-2 to -4-6 and radio frequency interference suppression according to EN 55011. The insulation test is performed at 2.5 kV for 1 minute. The overvoltage category is III. The enclosure protection rating is IP 40, and the terminals are IP 20. Creepage and clearance distances correspond to a rated impulse withstand voltage of 4 kV and pollution degree 2 (basic insulation) according to IEC 60664-1.
Operation and Maintenance
The relay is designed for continuous operation. Maintenance involves visual inspection of the switching position indicator and, if necessary, checking the terminal connections. The time delay can be adjusted at any time via the relative scale. Changing the time setting during the time interval may lead to unintended switching operations; therefore, adjustments should only be made in the resting state.