Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
AC 400 V 50 Hz
Time delay
without
Variant
Undervoltage relay. Closed circuit operation
The Dold voltage relay BA9036 AC50HZ 400V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of supply voltage to detect voltage dips or failures early, thereby increasing the operational safety of electrical installations. The device operates on the standby current principle, where the contacts are closed during normal operation and open in case of undervoltage. Adjustment is performed via rotary switches on the front panel, enabling user-friendly and precise setting of pickup and dropout values. The devices are designed for use in enclosures and have a width of 45 mm, making them suitable for standard control panels.
Applications
This relay is intended for applications in industrial and commercial environments where reliable voltage monitoring is required. Typical applications include monitoring supply networks for machines, drives, lighting systems, or safety functions. The ability to monitor both AC and DC voltage expands the range of applications. The devices comply with IEC/EN 60255-1, ensuring adherence to safety and functional requirements for measuring and protective devices in electrical installations.
Functions and Equipment in Detail
The BA9036 features 2 changeover contacts as output contacts, which can be used to control auxiliary functions or alarms. The contacts are rated for a thermal current of 6 A and meet switching capacities according to AC 15 (2 A / AC 230 V) and DC 13 (1 A / DC 24 V). The electrical life expectancy is 150,000 switching operations at 6 A and AC 230 V, while the mechanical life expectancy is 30 million switching operations. The pickup delay is adjustable between 0.5 and 10 seconds, with the delay only active when the voltage is above 60 % of the rated voltage. This allows for differentiated response to short-term voltage dips without triggering unnecessary operations.
Technology Explained Simply
The relay monitors the applied voltage in the range of 24 to 400 V AC or DC. The rated voltage is AC 400 V at 50 Hz. The adjustment ranges are between 0.85 and 1.05 times the rated voltage, with the variant /1_ _ enabling a range of 0.9 to 1.25 times the rated voltage. The hysteresis (dropout ratio) is 0.75 to 0.95 of the set value, ensuring stable switching behavior without oscillations. The repeatability accuracy is ±0.5 %, ensuring high precision in repeated measurements. The devices are designed for an operating temperature of -20 to +60 °C and can be continuously loaded up to 1.2 times the rated voltage.
Compatibility and Accessories
For DC voltages above 60 V, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. The necessary resistors are available as accessories, for example ZWS 20 SL 1.5 kΩ 20 W for DC 110 V. The devices can operate without auxiliary voltage, simplifying installation. LED indicators show operational readiness (upper LED) and activation of the output relay (lower LED), facilitating diagnostics during operation.
Mounting and Installation
The device is mounted in enclosures and is designed for installation on standard 35-mm rails. The connection terminals are clearly labeled, with terminal z reserved exclusively for the external resistor. Installation is performed without auxiliary voltage, simplifying wiring. The devices are designed for continuous operation and require no special maintenance, provided the connection terminals are clean and properly connected.
Operational Advantages
Early detection of voltage anomalies enables preventive maintenance and reduces downtime. The adjustable pickup and dropout values, as well as the time delay, allow customized adaptation to specific requirements. The LED indicators provide visual feedback on the operational status, speeding up troubleshooting during operation. The high mechanical and electrical life expectancy ensures long service life with minimal maintenance effort.