| Technical data |
| 1- / 2-channel | 1, 2 |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable screw terminals |
| Output contacts max. | 1 NC contact, 3 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 100 mm |
| Type | BN 5930.48 |
| Variant |
| Contact equipping | 3 NO contacts, 1 NC contact |
| Nominal voltage | DC 24 V |
| Approvals and Markings | TÜV |
The Dold BN5930.48 DC24V is a safety-oriented emergency stop module designed for use in industrial systems to safely interrupt safety circuits. It is particularly intended for the protection of personnel and machinery in applications involving emergency stop buttons and safety doors. The device is designed as a
safety relay and meets the requirements for safety functions in industrial automation. It features a
1- or 2-channel configuration, enabling flexible use in different safety architectures. The nominal voltage is
DC 24 V, making it suitable for standard industrial applications.
Applications
The BN5930.48 is used in systems where a safe response to emergency stop signals or the opening of safety doors is required. It is intended for use in machine controls, production systems, and other industrial environments where compliance with safety standards is mandatory. The module’s function is to safely disconnect drives, motors, or other hazardous movements as soon as an emergency stop signal or door opening is detected. The
safety function is supported by the integrated monitoring of the feedback circuit X1–X2, which can monitor external contactors.
Functions and Equipment in Detail
The device features a contact configuration with
3 normally open contacts (NO) and
1 normally closed contact (NC), enabling flexible wiring in safety circuits. The
removable screw terminals simplify installation and maintenance, as they can be removed and repositioned without tools. The
LED indicators for channel 1 and 2 allow visual monitoring of the operating status and support troubleshooting. The indicators show whether the respective channel is active or if a fault is present.
Technology Explained Simply
The BN5930.48 operates on the principle of a safety relay, which only activates the output when input conditions are met and no faults are present in the system. The
Performance Level (PL) e and
Category 4 according to EN ISO 13849-1 ensure a high safety performance required for critical applications. Additionally, the device meets the requirements for
SIL 3 according to IEC/EN 62061 and
SIL 3 according to IEC/EN 61508, confirming its reliability and fault-free operation in safety-critical systems. The
maximum thermal current Ith is 5 A, defining the maximum load capacity of the contacts and ensuring the device is not overloaded under normal operating conditions.
Compatibility and Accessories
The module is designed for use in systems connected to emergency stop buttons, safety doors, or other safety switches. The
feedback circuits X1–X2 enable monitoring of external contactors, thereby extending the safety function. It is compatible with standard terminal strips and can be mounted in enclosures with a
width of 100 mm. The
TÜV certification confirms compliance with applicable safety standards.
Mounting and Installation
Mounting is carried out in an enclosure or control unit. The removable screw terminals allow for easy and secure wiring. The terminal assignment is shown in the manufacturer’s wiring diagram, with the terminal labeling differing from the BN5983 model. Installation must follow the technical specifications in the datasheet, with correct wiring of safety circuits being crucial.
Advantages in Operation
The BN5930.48 provides high safety performance through the combination of PL e, Category 4, and SIL 3. The LED indicators and feedback circuit X1–X2 support diagnostics and maintenance. The removable terminals simplify installation and replacement. The device is designed for industrial environments and complies with applicable safety standards, ensuring reliable operation in critical applications.