| Technical data |
| 1- / 2-channel | 1 |
| Approvals | UL-Recognized |
| Cat. / PL acc. to EN ISO 13849-1 | 3/d |
| Connection | Screw terminals |
| Output contacts max. | 1 NC contact, 1 NO contact |
| SIL CL acc. to IEC/EN 62061 | 2 |
| SIL acc. to IEC/EN 62061 | 2 |
| Thermal current Ith max. | 8 A |
| Time delay max. | 30 s |
| Width | 45 mm |
| Type | BA 7924 |
| Variant |
| Contact equipping | 1 NC contact, 1 NO contact |
| Nominal voltage | AC 230 V |
| Time range | 0,5 - 5 s |
| Approvals and Markings | TÜV, CCC |
| Variant | 1 timing circuit, adjustable time |
The Dold delay module BA7924.21 AC230V 0,5-5S is an industrial safety relay module designed for delayed disconnection in control and protection systems. It features a drop-out delayed function, whereby the output does not switch off immediately after the input voltage is turned off, but after a user-adjustable delay time of 0.5 to 5 seconds. The device is designed for use in safety applications and can be used in conjunction with suitable switching devices or controls up to Category 3 and Performance Level d according to EN ISO 13849-1, as well as up to SIL 2 according to IEC/EN 62061. The contact configuration includes one normally open (NO) and one normally closed (NC) contact, which are mechanically interlocked to ensure a safe switching position. The connection technology uses screw terminals, and the module has a width of 45 mm, making it suitable for standard 35 mm control panels.
Applications
The delay module BA7924.21 is intended for use in industrial plants, particularly in safety control systems, where controlled and time-delayed disconnection of machines or drives is required. Examples include drive shutdown after operation ends, delay of emergency stop signals, or synchronization of process steps. The drop-out delayed function ensures that certain functions remain active for a defined period even after the input voltage is switched off, which is necessary in many safety applications.
Functions and Equipment in Detail
The module features an adjustable time range of 0.5 to 5 seconds, which can be set via a rotary control on the device. The maximum delay time is 30 seconds, although the variant specified here is limited to the 0.5–5 s range. The output contacts consist of one NO and one NC contact, mechanically interlocked to ensure a safe switching position. A switching position indicator allows for visual verification of the contact status. The device operates without auxiliary voltage, simplifying installation and increasing reliability.
Technology Explained Simply
The drop-out delayed function means that the relay output returns to its resting position only after the set delay time has elapsed following the interruption of the input voltage. This is particularly important in applications where immediate disconnection would be dangerous or disruptive to function. The mechanically interlocked contacts ensure that the NO and NC contacts are mechanically coupled, preventing any fault where both contacts open or close simultaneously. The screw terminals allow for a secure and durable connection with the wiring. The width of 45 mm corresponds to the standard for DIN rail mounting, enabling easy integration into existing control panels.
Compatibility and Accessories
The module is designed for use in safety systems and can be used in conjunction with suitable switching devices or controls. It is available in various variants, including models with one or two separate time circuits, as well as redundant time circuits. The variant described here, BA7924.21 AC230V 0,5-5S, features a single time circuit with an adjustable delay time. The certifications TÜV, CCC, and UL-Recognized confirm compliance with international safety standards. The standards EN ISO 13849-1 and IEC/EN 62061 define the safety requirements that the device meets.
Mounting and Installation
Mounting is done on a standard DIN rail (35 mm) in control panels. The width of 45 mm allows placement next to other components without additional space requirements. The terminal connections are designed for secure connections, with a maximum thermal current rating (Ith) of 8 A. Installation requires no additional tools, as the device operates without auxiliary voltage. The delay time is adjusted via a rotary control on the device, which is accessible during operation.
Operational Advantages
The drop-out delayed function provides controlled disconnection, which is required in many industrial applications. The mechanically interlocked contacts increase safety by preventing simultaneous opening or closing of contacts. The switching position indicator allows for quick visual inspection of the operating status. Operation without auxiliary voltage reduces installation complexity and increases system reliability. Compliance with safety standards EN ISO 13849-1 and IEC/EN 62061 makes the module suitable for critical applications.
Safety Technical Data
The device meets the requirements of safety standards EN ISO 13849-1 (Category 3, PL d) and IEC/EN 62061 (SIL 2). These certifications confirm that the module can be used in safety systems requiring high reliability and fault tolerance. The certifications TÜV, CCC, and UL-Recognized highlight the international recognition of the product.
Certifications and Markings
The module carries the certifications TÜV, CCC, and UL-Recognized, confirming compliance with respective safety and quality standards. These markings are relevant for use in various markets and facilitate the approval of installations in which the module is used.
Maintenance and Repair
Maintenance of the module is minimal. The contacts are wear-resistant, and the screw terminals require no regular maintenance. In case of faults, the delay time setting and the connections of the wiring should be checked first.
Application Example
A typical application example is the delayed shutdown of a drive in a production plant. After the control is switched off, the drive should continue running for 3 seconds to ensure the machine comes to a complete stop. The BA7924.21 module enables this function through its adjustable delay time of 0.5 to 5 seconds.
Safety Requirements
The module meets the requirements of standards EN ISO 13849-1 (Category 3, PL d) and IEC/EN 62061 (SIL 2). These certifications confirm that the module can be used in safety systems requiring high reliability and fault tolerance. The certifications TÜV, CCC, and UL-Recognized highlight the international recognition of the product.
Certifications and Markings
The module carries the certifications TÜV, CCC, and UL-Recognized, confirming compliance with respective safety and quality standards. These markings are relevant for use in various markets and facilitate the approval of installations in which the module is used.
Maintenance and Repair
Maintenance of the module is minimal. The contacts are wear-resistant, and the screw terminals require no regular maintenance. In case of faults, the delay time setting and the connections of the wiring should be checked first.
Application Example
A typical application example is the delayed shutdown of a drive in a production plant. After the control is switched off, the drive should continue running for 3 seconds to ensure the machine comes to a complete stop. The BA7924.21 module enables this function through its adjustable delay time of 0.5 to 5 seconds.