Further information for Dold 0039920 AK9840.82 3AC50/60Hz 480V asymmetrical relay
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Measuring range max.
3 AC 690 V
Output contacts
2 C/O contacts
Standard measuring range
3 AC 400 V
Width
70 mm
Type
AK 9840
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 480 V 50/60 Hz
The asymmetry relay AK 9840.82 from Dold is a monitoring device for three-phase networks, detecting voltage asymmetry, undervoltage, phase failure, and incorrect phase sequence. It ensures operational safety in industrial plants and is installed in enclosures. The device operates on the stand-by current principle, where the output relay is activated during normal operation and deactivated upon detection of a fault. The function is designed for nominal voltages of 3 AC 110 to 690 V, with the specified variant intended for 3 AC 480 V 50/60 Hz.
Applications
This relay is suitable for monitoring three-phase networks in industrial environments, particularly in plants with thyristor installations, automatic reactive power compensation systems, or emergency power supplies exhibiting high harmonic content. It can also be used for monitoring networks with a neutral conductor, although the N connection is not required. Applications include, for example, automatic switching to battery-powered emergency lighting when network voltage drops by 30%, in accordance with VDE 0108.
Functions and Equipment in Detail
The device detects voltage asymmetry by measuring the difference between two voltages and does not respond to symmetrical voltage drops as long as they do not fall below the set undervoltage limit of 0.7 U_N. The response delay is continuously adjustable between 0.5 and 5 seconds. In the case of incorrect phase sequence, tripping occurs immediately. Undervoltage detection is also integrated, with detection occurring either as asymmetry (delayed) or incorrect phase sequence (immediate), depending on network conditions. The status indication is provided by an LED, which lights up when the output relay is activated.
Technology Explained Simply
Measurement is performed by determining the arithmetic mean of the three phase voltages. The device responds to asymmetric voltage changes caused by uneven network loading or failure of a line conductor. The setpoints for voltage asymmetry are adjustable between 5 and 20% of the nominal voltage. The reset hysteresis is fixed at 0.98. The device is designed for frequencies of 50/60 Hz, with a frequency range of ±5% or ±10% for up to 1.5 seconds. The nominal power consumption is ≤ 7.1 VA.
Compatibility and Accessories
The asymmetry relay is designed for use in three-phase networks and can also be used in networks with a neutral conductor, although the N connection is not required. In this case, the nominal voltage must be converted to line-to-line voltage. It is suitable for networks with high harmonic content, as the measurement principle does not cause falsification of the setpoints. The contact configuration includes two changeover contacts, which can be used for controlling auxiliary functions or alarms.
Mounting and Installation
The device is designed for mounting in enclosures and has a width of 70 mm. The connection terminals are intended for direct connection to the phases to be monitored (L1, L2, L3). The LED indicator shows the contact position and facilitates visual inspection of the operating status. Installation requires no additional auxiliary voltage, simplifying wiring.
Operational Advantages
Early detection of voltage asymmetry, undervoltage, or incorrect phase sequence enables preventive maintenance and prevents costly damage. The adjustable response delay and undervoltage detection increase the reliability of the system. The LED indicator provides quick visual control of the operating status. The device is compliant with IEC/EN 60255-1 and designed for use in industrial environments.