Further information for Dold 0039884 BA9043/001 3AC50/60HZ 400V undervoltage relay
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 400 V
Time delay
without
Approvals and Markings
UKCA, CCC
Variant
For 3p3w systems
The undervoltage relay BA9043/001 from Dold is a 3-phase monitoring device for three-phase networks without a neutral conductor. It is designed for continuous monitoring of the supply voltage and de-energizes output contacts in case of undervoltage to prevent damage to connected devices or machinery. The device is rated for nominal voltages of 3AC 400 V and operates within a frequency range of 50 to 400 Hz. It is specifically designed for use in industrial and railway applications, where reliable voltage monitoring is critical for operational safety.
Applications
This relay is used in industrial plants, power supply technology, and rail vehicle technology, where continuous monitoring of the supply voltage is required. It is particularly suitable for systems where a voltage interruption could lead to production downtime or damage to electrical installations. The enclosure design for enclosures allows for easy mounting on DIN rail and integration into existing control systems.
Functions and Equipment in Detail
The device monitors voltage via arithmetic mean measurement. For the BA9043/001 variant, designed for networks without a neutral conductor, phases L1 and L2 are measured against L3. The pickup and dropout values are adjusted via rotary potentiometers on the front panel, enabling user-friendly and precise adaptation to specific applications. The pickup value is continuously adjustable between 0.85 and 1.05 of the nominal voltage, with hysteresis ranging from 0.75 to 0.95 of the pickup value. The device features 2 changeover contacts as output contacts, rated for switching operations in AC 15 and DC 13 categories. The maximum thermal current rating per contact is 6 A.
Technology Explained Simply
The relay operates on the standby current principle, meaning the output relay is not activated during normal operation and only de-energizes in case of undervoltage. This prevents unnecessary switching operations and increases contact life. The LED indicators show operational readiness (red LED) and activation of the output relay (green LED). The device is harmonic-insensitive, meaning it operates reliably even with distorted voltage waveforms. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The maximum operating altitude is limited to 2000 m above sea level.
Compatibility and Accessories
The relay is suitable for networks with or without a neutral conductor, with the BA9043/001 variant specifically designed for systems without a neutral conductor. It is compliant with IEC/EN 60255-1 and carries UKCA and CCC certifications. The connection terminals are designed for 2 x 2.5 mm² rigid or 2 x 1.5 mm² flexible conductors with heat-shrink tubing. Mounting is done on DIN rail according to IEC/EN 60715.
Mounting and Installation
Installation is performed by securing the device onto a DIN rail within the enclosure. The connection terminals are equipped with M3.5 plus-minus screws with self-lifting inserts, to be tightened with a torque of 0.8 Nm. Dimensions are 45 mm width, 73 mm height, and 132 mm depth. Wiring is to be carried out according to the data sheet, connecting phases L1, L2, and L3 to the corresponding input terminals.
Operational Advantages
The precise adjustability of pickup and dropout values, combined with LED indicators, enables quick fault localization. The high mechanical life of over 30 million switching operations and electrical life of 200,000 switching operations at 3 A/AC 230 V ensure long-term operational reliability. Compliance with IEC/EN 60255-1 and UKCA and CCC certifications guarantee adherence to safety and quality requirements.