| Technical data |
| 1- / 2-channel | 1 |
| Approvals | UL-Recognized |
| Cat. / PL acc. to EN ISO 13849-1 | 3/d |
| Connection | Screw terminals |
| Output contacts max. | 1 NC contact, 1 NO contact |
| SIL CL acc. to IEC/EN 62061 | 2 |
| SIL acc. to IEC/EN 62061 | 2 |
| Thermal current Ith max. | 8 A |
| Time delay max. | 30 s |
| Width | 45 mm |
| Type | BA 7924 |
| Variant |
| Contact equipping | 1 NC contact, 1 NO contact |
| Nominal voltage | AC 230 V |
| Time range | 0,3 - 3 s |
| Approvals and Markings | TÜV, CCC |
| Variant | 1 timing circuit, adjustable time |
The Dold delay module BA7924.21 AC230V 0,3-3S is an industrial safety relay module for implementing delayed shutdowns in control and protection systems. It serves as a component in safety-critical installations, where a controlled, time-delayed response to input signals is required, for example in machine control or emergency shutdowns. The device is designed for use in safety applications and complies with the requirements of standards EN ISO 13849-1 and IEC/EN 62061. It features a
drop-out delayed function, in which the output does not return immediately after the input signal is switched off, but after an adjustable delay of 0.3 to 3 seconds. The maximum time delay is 30 seconds, although the current variant is fixed to the range of 0.3 to 3 seconds. The
rated voltage is AC 230 V, and the module is connected via screw terminals.
Applications
The module is intended for use in industrial control systems and safety installations, particularly in systems designed according to EN ISO 13849-1 up to Category 3 and Performance Level d. It can be used in conjunction with suitable switching devices or control systems to implement safety-relevant functions such as emergency shutdowns, protection functions, or time-controlled shutdown processes. The
forced-guided contacts ensure a secure switching function, even in the event of mechanical faults. The switching position indicator allows for visual verification of the current state of the output contacts.
Functions and Equipment in Detail
The device features a
contact configuration with one normally open (NO) and one normally closed (NC) contact, both implemented as forced-guided contacts. This design ensures that the contacts are mechanically linked, thereby minimizing the risk of malfunction due to mechanical defects. The
connection technology is via screw terminals, which enable a secure and durable connection. The maximum thermal current rating (Ith) is 8 A, defining the contact load capacity for operation in industrial environments. The module width is 45 mm, allowing installation in standard 35 mm control panels.
Technology Explained Simply
The
drop-out delayed function means that the output signal is switched off not immediately, but after a pre-set delay time following the deactivation of the input signal. This is necessary, for example, to safely shut down motors or other drives without them stopping abruptly. The time delay in the BA7924.21 variant is fixed to the range of 0.3 to 3 seconds. The maximum delay of 30 seconds is available for other variants of the module, but not for this specific version. The
safety functions are certified according to standards EN ISO 13849-1 (Category 3, PL d) and IEC/EN 62061 (SIL 2), confirming suitability for safety-critical applications. The certifications TÜV, CCC, and UL-Recognized highlight its international usability.
Compatibility and Accessories
The module is designed for use in safety installations and can be used in conjunction with suitable switching devices or control systems. It is available in various variants, including models with redundant timing circuits or with 2 separate timing circuits. The module width of 45 mm allows installation in standard control panels. The note “optionally also available in housing for I-distributors” refers to other variants of the module, not to this specific version.
Mounting and Installation
Mounting is done in standard control panels with a module width of 45 mm. The connection terminals are designed for a secure connection. The switching position indicator enables visual monitoring of the operating status. Installation does not require auxiliary voltage, as the module can operate without external auxiliary voltage.
Operational Advantages
The
forced-guided contacts increase safety by minimizing the risk of malfunction due to mechanical defects. The
drop-out delayed function enables controlled shutdowns, which are required in many industrial applications. The certifications according to EN ISO 13849-1 and IEC/EN 62061 guarantee suitability for safety-critical installations. The screw terminals ensure a robust and durable connection. The module width of 45 mm allows easy integration into existing control panels.