Dold 0039676, EAN: 4030641396763

Dold 0039676 BA9043/3PH/N undervoltage relay 230V

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0039676 BA9043/3PH/N undervoltage relay 230V

Lieske Part No. 239793
Mfg Part No 0039676
EAN-Code 4030641396763
Manufacturer Dold
Here only 270,07 EUR
321,38 EUR incl. VAT

Further information for Dold 0039676 BA9043/3PH/N undervoltage relay 230V

Technical data
1- / 3-phase3
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.3/N AC 690 / 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9043
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3/N 230/400 V
Time delaywithout
Approvals and MarkingsUKCA, CCC
VariantFor 3p4w systems
The undervoltage relay BA9043/3PH/N from Dold is a 3-phase monitoring device for three-phase networks with neutral conductor. It is designed for continuous monitoring of network voltage and disconnects connected loads in case of undervoltage or voltage loss to prevent damage. The device is designed for use in industrial and railway applications and complies with the standard IEC/EN 60255-1. Measurement is performed via arithmetic mean calculation, where each phase is measured against the neutral conductor. The setting of pickup and dropout values is done via rotary potentiometers on the device front, enabling user-friendly and precise adjustment for the respective application.

Applications

The relay is designed for networks with a nominal voltage of 3/N AC 230/400 V and can monitor voltages from 3/N AC 100/57 V to 690/400 V. It is suitable for frequencies from 50 to 400 Hz and is therefore also suitable for systems with variable frequency, such as those found in rail vehicle technology. The application is in enclosures with DIN rail, where the width of 45 mm enables compact mounting. The devices are designed for continuous operation and function in a temperature range from -20 °C to +60 °C.

Functions and Equipment in Detail

The device features 2 changeover contacts as output contacts, designed for switching operations with a thermal current of up to 6 A per contact. The switching capacity is 2 A/AC 230 V (make) and 1 A/AC 230 V (break) according to AC 15. The electrical life expectancy is at least 200,000 switching operations at 3 A/AC 230 V. The contacts are designed according to the rest current principle, meaning the output relay is not activated in the event of a fault. This prevents unwanted switching operations during voltage failure. Indication is provided via LEDs: a red LED indicates readiness for operation, while a green LED signals the activated state of the output relay.

Technology Explained Simply

Voltage measurement is performed via arithmetic mean calculation, where the voltage of each phase is measured against the neutral conductor. This enables precise and reliable monitoring, even under unbalanced loads. The device is harmonic-insensitive, meaning it operates reliably even under network distortions caused by nonlinear loads. The pickup delay is inactive, as the variant is equipped without time delay. Below 0.4 times nominal voltage, the relay drops out immediately. The adjustment range for the pickup value is between 0.85 and 1.05 times nominal voltage, and the hysteresis is 0.75 to 0.95 of the pickup value.

Compatibility and Accessories

The relay is designed for networks with a neutral conductor and can be used in 3p4w systems. The terminal connections are rated for 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded), with a stripping length of 10 mm. Mounting is done on DIN rail according to IEC/EN 60715. The certifications include UKCA and CCC.

Mounting and Installation

Mounting is performed in enclosures on DIN rail. The terminals are equipped with plus-minus screws M3.5 with self-lifting inserts, to be tightened with a torque of 0.8 Nm. The connection markings are L1, L2, L3 and N for the network to be monitored, and 11, 12, 14 and 21, 22, 24 for the two changeover contacts. The devices are designed for use in environments with an operating altitude up to 2000 m above sea level.

Operational Advantages

Precise voltage monitoring and easy adjustment of pickup values enable preventive maintenance. Rapid fault localization via LED indicators and reliability under harmonic load increase productivity and reduce downtime. The device is designed for use in industrial and railway applications, where high availability and reliability are required. Compliance with the standard IEC/EN 60255-1 ensures electrical safety and functionality in critical applications.