| Technical data |
| Enclosure design | Distribution board |
| Output contacts | 1 C/O contact |
| Time function(s) | Fleeting on make |
| Width | 17,5 mm |
| Type | IK 7815 |
| Variant |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC/DC 12 V |
| Time range | 1 - 10 s |
| Variant | Fleeting action |
The Dold IK7815.71 AC/DC12V 1-10S is an industrial time-delay relay for time-dependent control applications in installation and industrial distribution systems. It is used for time-delayed switching of loads, for example in lighting systems, pumps or motors, where a controlled switching delay is required. The device operates according to the standard IEC/EN 61812-1 and features an
on-delay function, where the output contact switches after a configurable delay of 1 to 10 seconds following the application of input voltage. The
delay time is continuously adjustable on a relative scale, with a repeat accuracy of ≤ ±1 %. An
LED indicator signals the closed state of the output relay (contacts 15–18). The contact configuration includes a
1 changeover contact, rated for switching operations with a nominal operating voltage of AC 250 V. The contact material is AgSnO₂, ensuring high switching durability and low contamination.
Applications include industrial control systems, building automation, machine construction and plants where time-controlled activation of consumers is necessary. The relay is designed for use in
installation distributors, with the housing type IK 7815 featuring a depth of 58 mm and bottom-mounted connection terminals, suitable for distributors according to DIN 43880. The width is 17.5 mm, enabling compact mounting in standard distributors. The nominal voltage is AC/DC 12 V, with an operating voltage range of 0.8 to 1.1 times nominal voltage. For battery operation, the range is 0.9 to 1.25 times nominal voltage. The drop-out voltage is 15 % of nominal voltage.
Functions and equipment in detail include a mechanical life of over 30 million switching operations and an electrical life of 500,000 switching operations at 3 A and AC 230 V (AC 15). The device is designed for continuous operation and can be operated at ambient temperatures from -20 °C to +60 °C. The relative humidity is up to 95 % at 40 °C. Switching capacity is 10 A/AC 230 V for make contacts and 5 A/AC 230 V for break contacts according to IEC/EN 60947-5-1. The maximum incandescent lamp load is 1200 W. Short-circuit withstand is defined with a maximum fuse rating of 10 A gG/gL and a circuit breaker with tripping characteristic B16.
Technology explained simply shows that the time-delay relay enables delayed switching, where the contact closes only after the set time has elapsed. Adjustment is continuous on a relative scale, with changes taking effect immediately during the timing process. The re-arming time is less than 60 ms at 50/100 Hz. Voltage influence is ≤ 1 % at 0.8 to 1.1 times nominal voltage, and temperature influence is 0.05 % per Kelvin. The insulation test voltage is 2.5 kV for 1 minute. The housing protection rating is IP 40, and the terminals are IP 20, providing protection against touch and dust, but not against water.
Compatibility and accessories refer to the two housing types IK 7815 and SK 7815, with the SK variant intended for enclosures with mounting plate and cable duct. The connection terminals are designed for secure connections. The device is available for various nominal voltages, including AC/DC 12 V, AC/DC 24 V, AC 110–127 V and AC 220–240 V, with the variant described here being AC/DC 12 V. The input voltage can also be in the range of 0.9 to 1.25 times nominal voltage during battery operation.
Mounting and installation is carried out in standard installation distributors according to DIN 43880. The bottom-mounted terminals allow for easy and secure connections. The width of 17.5 mm fits standard distributor modules. Mounting is done by inserting into the distributor rail, with the depth of 58 mm to be considered. The terminals are designed for secure connections, with terminal markings A1/A2 for input supply and 15/16/18 for the changeover contact.
Operational advantages include high repeat accuracy, long service life and simple adjustment of the delay time. The LED indicator enables visual monitoring of the contact status. The device is designed for use in industrial environments where reliability and longevity are critical. Compliance with the standard IEC/EN 61812-1 ensures standardized quality and safety. EMC requirements are met, with tested immunity against electrostatic discharge (8 kV), HF radiation and fast transients (4 kV). Radio frequency interference suppression complies with emission limit class B according to EN 55011.