Further information for Dold 0037444 coupling relay CA3056.01/101 220-240V AC50/60Hz
Technical data
Enclosure design
Switch cabinet
Output contacts max.
1 NC contact, 1 NO contact
Thermal current Ith max.
5 A
Width
11,5 mm
Type
CA 3056
Initiator triggering
Suppressor circuit on the coil input
Variant
Contact equipping
1 NO contact
Nominal voltage
AC 220 - 240 V
Variant
Input circuit with MOV. For switching low loads
The coupling relay CA3056.01/101 AC50/60HZ 220-240V from Dold is an industrial component for contact multiplication and serves as an interface between control and power level in electrical switching systems. It is specifically designed for use in enclosures and enables the control of loads via a galvanically isolated circuit. The width of 11.5 mm allows for compact mounting in standard switchboards. The device is rated for a nominal voltage of AC 220–240 V and operates at a nominal frequency of 50/60 Hz. The coil is equipped with a protective circuit that integrates a MOV (Metal-Oxide Varistor) at the input to increase surge voltage resistance and ensure reliability during transient voltage spikes.
Applications
This relay is particularly suitable for applications requiring potential isolation, such as in automation technology, building automation, or industrial control systems. It is used to transmit signals from control devices (e.g. PLCs, SPS) to power components (e.g. contactors, motors, heaters). The variant CA3056.01/101 is specifically designed for switching small loads, with contacts coated with a 5 μm gold layer to minimize contact contamination at low currents. The maximum switching values are 3 A/AC 230 V for closing contacts and 1 A/AC 230 V for opening contacts according to AC 15, where the gold coating may burn off at higher loads, rendering the device unsuitable for small loads thereafter.
Functions and Features in Detail
The relay features an LED indicator that lights up when energized, visually signaling the operating status. The contact configuration includes one closing contact (1 NO), with a maximum contact arrangement of 1 closing and 1 opening contact. The initiator actuation enables integration into control systems that operate with special actuation signals. The thermal current rating (Ith) is up to 5 A, defining the continuous load capacity of the contacts. The electrical life expectancy exceeds 800,000 switching operations at 3 A/AC 230 V, while the mechanical life expectancy exceeds 30 million switching operations, indicating high operational reliability.
Technology Explained Simply
The protective circuit at the coil input with MOV protects the relay from transient voltage spikes caused by switching operations or atmospheric discharges. The rated insulation voltage is 300 V, and the overvoltage category III is suitable for applications in industrial environments. The safe separation according to IEC/EN 61140 and IEC/EN 60947-1 with a rated impulse voltage of 6 kV/2 between input and output ensures galvanic isolation, which is required for safety in electrical installations. The operating temperature range is from -25 °C to +60 °C, and the operating altitude is limited to a maximum of 2000 m above sea level.
Compatibility and Accessories
The relay complies with IEC/EN 60947-5-1 and can be used in systems requiring this standard. It is compatible with control devices providing an operating voltage of AC 220–240 V. The variant CA3056.01/101 is specifically designed for small loads, where the gold coating of the contacts improves switching quality at low currents. Combination with other variants of the CA 3056 series (e.g. with 2 closing contacts or changeover contacts) is possible if the application requires it.
Mounting and Installation
The relay is mounted in enclosures and is designed for mounting on standard 35 mm rails. The connection terminals are designed for secure cable connections, with the maximum short-circuit withstand limited by a maximum fuse rating of 6 A gG/gL. Mounting requires no additional tools, as terminals can be connected directly. The LED operating indicator facilitates commissioning and maintenance.
Operational Advantages
The combination of compact design, high service life, and integrated protective circuit makes the relay a reliable component in industrial controls. The LED indicator allows for quick diagnosis of the operating status. The safe separation and galvanic isolation between control and power level increase the safety of the installation. The use of MOV at the input protects the device from voltage spikes, extending its service life and reducing failures. The maximum switching frequency is 20 switching operations per second, which is sufficient for dynamic applications.