| Technical data |
| Enclosure design | Distribution board |
| Output contacts | 1 C/O contact |
| Time function(s) | Fleeting on make |
| Width | 17,5 mm |
| Type | IK 7815 |
| Variant |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC 220 - 240 V |
| Time range | 1 - 10 s |
| Variant | Fleeting action |
The Dold IK7815.71 AC220-240V 1-10S is an
on-delay timer relay of the IK 7815 series, specifically designed for time-controlled applications in installation and industrial distributors according to DIN 43880. The device is used for time-delayed switching of loads, for example, in pumps, lighting, or heating systems, where delayed activation is required. It features a
17.5 mm mounting width and is designed for use in standard distributor enclosures. The rated voltage is
AC 220–240 V, with operation guaranteed within a voltage range of 0.8 to 1.1 times the rated voltage. The time function is configured as
on-delay, meaning the output contact closes only after the set delay time has elapsed, once the input voltage pulse is activated.
Applications
This relay is suitable for use in industrial and commercial installations where precise, time-controlled switching functions are required. Typical applications include delaying the start of motors to reduce mechanical stress, or time-delayed switching of lighting systems. The
repeatability ≤ ±1 % ensures high reliability during repeated switching operations. The
delay time is adjustable between
1 and 10 seconds, with stepless adjustment on a relative scale. Changing the time setting during the timing process may cause unintended switching operations; therefore, adjustment is recommended when the device is at rest.
Functions and Equipment in Detail
The device features
1 changeover contact as the output contact, consisting of one normally open and one normally closed contact, allowing flexible integration into circuits requiring changeover contacts. The contact material is
AgSnO₂, ensuring good switching performance and long service life for loads such as incandescent lamps (up to 1200 W) and electrical consumers. The
LED indicator signals the contact position: it lights up when the output contact (15–18) is closed, indicating that the relay output is activated. The
rated consumption is 3.5 VA at AC 230 V, 50 Hz, representing low energy demand on the control device.
Technology Explained Simply
The time function is based on an electronic timer that initiates a delay of 1 to 10 seconds after the input voltage (A1/A2) is applied. During this time, the output contact remains open. After the set time has elapsed, the contact closes and activates the connected load. The
reset time is less than 60 ms at 50/100 Hz, meaning the device is quickly ready for the next switching operation after deactivation. The
temperature dependence of the time function is 0.05 % per Kelvin, ensuring stable performance over a wide temperature range. The
voltage influence on the time function is ≤ 1 % within the range of 0.8 to 1.1 times the rated voltage, ensuring reliable operation even with voltage fluctuations.
Compatibility and Accessories
The device is available in the
IK 7815 form factor, featuring a depth of 58 mm and bottom-mounted terminals, specifically designed for installation and industrial distributors according to DIN 43880. It is not compatible with the SK 7815 form factor, which is designed for enclosures with mounting plate and cable duct. The terminals are designed for secure connection with wires. The
switching capacity according to AC 15 is 10 A for the closing contact and 5 A for the opening contact at AC 230 V. The maximum thermal current load is 10 A, with the total current limit curve to be observed. The
short-circuit withstand capability requires a maximum fuse rating of 10 A gG/gL or an automatic circuit breaker with B16 tripping characteristic.
Mounting and Installation
The relay is mounted in standard distributor enclosures, with the bottom-mounted terminals enabling direct connection to the wiring. Installation is carried out by mounting on the appropriate rail (DIN rail) within the distributor. The
operating temperature ranges from -20 °C to +60 °C, and the
storage temperature ranges from -25 °C to +70 °C. The
relative humidity must not exceed 95 % at 40 °C. The
protection rating of the housing is
IP 40, providing protection against touch with fingers and against solid objects larger than 1 mm. The terminals are protected to
IP 20, meaning protection against touch with a 12.5 mm diameter rod. The device is designed for
continuous operation and can be operated at altitudes below 2000 m above sea level.
Advantages in Operation
The high
repeatability and low
temperature dependence of the time function ensure precise and reliable switching performance. The
LED indicator allows for easy visual monitoring of the operating status. The
stepless adjustment of the delay time enables flexible adaptation to different applications. The
low energy consumption and high
mechanical life (> 30 million switching operations) make the device a low-maintenance solution for industrial control tasks. Compliance with the standard
IEC/EN 61812-1 ensures conformity with international standards for time relays.