Dold 0036482, EAN: 4030641364823

Dold 0036482 BA9039.12/100 DC24V motor protection switch

Industrial Material > Control devices / Pilot devices > Motor protection switch

Dold 0036482 BA9039.12/100 DC24V motor protection switch

Lieske Part No. 1312999
Mfg Part No 0036482
EAN-Code 4030641364823
Manufacturer Dold
Here only 239,87 EUR
285,45 EUR incl. VAT

Further information for Dold 0036482 BA9039.12/100 DC24V motor protection switch

Technical data
ClassificationThermistor-Motorschutz
Enclosure designSwitch cabinet
Measuring range max.> 3 kΩ
Output contacts2 C/O contacts
Width45 mm
TypeBA 9039
Variant
Auxiliary voltageDC 24 V
Contact equipping2 changeover contacts
VariantWith electromechanical reset facility. No-voltage safe
The Dold motor protection relay BA9039.12/100 DC24V is a thermistor-based motor protection device designed to prevent thermal overloads in electric motors. It protects against damage caused by high switching frequency, heavy start-up, single-phase operation, impaired cooling, or high ambient temperature. The device is designed for use in enclosures and has a width of 45 mm, making it suitable for standard control panels. It operates on the no-current principle, where the output relay is not activated in the event of a fault, ensuring safe disconnection.

Applications
This relay is intended for use in industrial plants, particularly in drive technology and machine building. It monitors the temperature of electric motors via thermistors and responds when the pickup temperature of 3 kΩ ± 500 Ω is reached. The reset temperature is 1.8 kΩ ± 200 Ω, enabling hysteresis behavior to avoid unwanted switching operations. The maximum number of thermistors that can be connected is six, with a measurement circuit load of less than 3 mW (at 1.5 kΩ). The measurement voltage is 2 V at a resistance of 1.5 kΩ.

Functions and Features in Detail
The device features two changeover contacts as output contacts, which can be used to control auxiliary circuits. The contact configuration allows integration into existing circuits. A green LED indicates a fault-free state, while a red LED indicates operational status. The re-energizing lockout is electromechanical and voltage-fail-safe, meaning the state is maintained even after a power failure. The reset function can only be activated manually via a reset button, preventing uncontrolled re-energization.

Technology Explained Simply
The relay monitors the resistance value of the connected thermistors. When the pickup value of 3 kΩ ± 500 Ω is reached, the output relay is de-energized, disconnecting the motor from the power supply. The reset temperature of 1.8 kΩ ± 200 Ω ensures the relay is only re-energized once the temperature has sufficiently decreased. Wire break and short-circuit detection in the measurement circuit protects against malfunctions caused by defective or damaged sensor leads. The auxiliary voltage is DC 24 V, with a voltage range coverage of DC 0.9 to 1.25 UH (at 10 % residual ripple). The device consumes a nominal power of 1.2 W at DC 24 V.

Compatibility and Accessories
The relay is designed for use with thermistors, with 1 to 6 units connectable. The terminal clamps are rated for conductor cross-sections of 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded wire with sleeve according to DIN 46228). The clamps are equipped with self-lifting connection washers to ensure a secure connection. Terminal markings comply with standard EN 50005. Mounting is done via a DIN rail according to IEC/EN 60715.

Mounting and Installation
Installation is carried out in an enclosure, with the device mounted on a DIN rail. The terminal clamps are designed for connection with solid or stranded conductors. The stripping length is 10 mm, and the maximum tightening torque for the clamps is 0.8 Nm. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is also from -20 °C to +60 °C. The operating altitude is limited to below 2000 m.

Operational Advantages
The relay provides reliable monitoring of motor heat and protects against thermal damage. The voltage-fail-safe re-energizing lockout prevents unintended re-energization after a power failure. The LED indicators allow for quick visual status checks. Galvanic isolation between auxiliary voltage and measurement circuit is not present in the DC 24 V version, which must be considered during installation. The mechanical life is 30 million switching operations, and the electrical life at 3 A and AC 230 V is 800,000 switching operations. Short-circuit resistance is ensured with a maximum fuse rating of 4 A gG/gL according to IEC/EN 60947-5-1. The enclosure protection rating is IP 40, and the terminals are rated IP 20. EMC requirements comply with standards IEC/EN 61000-4-2 to -6, and radio frequency interference is within Class B limits according to EN 55011. The device is certified according to DIN VDE 0660 Part 302 (pr EN 60 947-8) and Part 303.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1312999
qrcode für Dold 0036482 BA9039.12/100 DC24V motor protection switch