| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 72 mm |
| Type | EF 7666 |
| Variant |
| Contact equipping | 1 changeover contact delayed, 1 changeover undelayed |
| Nominal voltage | AC 24 V |
| Time range | 0,15 - 1000 s |
The Dold time relay EF7666.32 is a delayed-release industrial time relay for front panel mounting, designed for a rated voltage of AC 24 V and a frequency of 50/60 Hz. It is used for time-delayed control of electrical loads, for example, to account for the coast-down behavior of motors or for controlled shutdown of system components. The device features a purely mechanical timing mechanism, which is adjusted via a continuous rotary switch on the front, enabling precise and flexible adaptation to various applications.
Applications
This time relay is designed for industrial control tasks requiring a delayed release function. Typical applications include controlling pumps, fans, lighting systems, or other system components that must continue running or be switched off for a specific time after the control signal is removed. Its use in automation technology, manufacturing technology, or building automation is common.
Functions and Features in Detail
The device provides contact configuration with one delayed changeover contact and one instantaneous changeover contact. The delayed contacts switch only after the set delay time has elapsed, while the instantaneous contacts react immediately when the control signal is applied. The time delay can be set between 0.15 and 1000 seconds, with six switchable time ranges available. Adjustment is made via a continuous rotary switch on the front, positioned on an absolute scale. Repeatability is ≤ ± 0.5 % of the scale end value, and for times of 3 and 6 seconds, ≤ ± 1 %. A timing indicator allows visual monitoring of the timing process. The device is voltage failure-safe, meaning it remains in its output position during power failure.
Technology Explained Simply
The timing mechanism is based on a purely mechanical principle, requiring no electronic components. The delay is generated by a mechanical clockwork system, controlled via an adjustment knob on the front. Contacts operate with an actuation time of < 35 ms and a release time of < 60 ms. The rated operating voltage is AC 250 V, and the thermal current rating is 4 A. Electrical life expectancy is at least 100,000 switching operations at 3 A and AC 230 V, and at least 500,000 switching operations at 1 A and AC 230 V. Mechanical life exceeds 30 million switching operations or 15,000 operating hours.
Compatibility and Accessories
The device is designed for use in control systems with AC 24 V and complies with standard EN 61812-1. It is intended for front panel mounting and has a width of 72 mm. The front panel is spray water protected and meets protection class IP 65, enabling use in outdoor or damp environments. Contact materials consist of AgNi with a gold plating of 0.2 μm, ensuring high switching durability and corrosion resistance. The maximum permissible switching frequency is 3000 switching operations per hour.
Mounting and Installation
The time relay is installed in a front panel with a mounting width of 72 mm. The terminal clamps are designed for connection to wires, and electrical connections are made via terminals A1/A2 (control voltage) and B1/B2 (control signal). The delay time is adjusted using the rotary switch on the front. Mounting requires no additional tools, as the device is standardly designed for front panel mounting.
Operational Advantages
The combination of wide adjustment range, high repeatability, and mechanical reliability makes this device a robust solution for industrial applications. Front-side adjustment allows for easy and quick modification of the delay time, even during operation. The IP 65 protection class ensures high environmental resistance, and voltage failure safety ensures safe operation. Mechanical life and high switching durability guarantee long service life under industrial conditions.