Further information for Dold 0034310 voltage relay BA9037.12/011AC50/60HZ240V1-20S
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9037
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
AC 240 V
Time delay
1 - 20 s
Variant
With adjustable time delay
The voltage relay BA9037.12/011AC50/60HZ240V1-20S from Dold is an industrial-grade measuring and monitoring device for controlling DC or AC voltage networks. It is used to detect under- and over-voltages in single-phase systems and enables early response to voltage deviations, preventing damage to connected devices or systems. The device operates on the rest current principle, where the output relay is not activated in the event of a fault, ensuring safe and reliable operation.
Applications
This relay is suitable for use in industrial plants, power supply systems, and machine controls where continuous voltage monitoring is required. It monitors voltages in the range of 24 to 400 V AC/DC and is designed for continuous operation. The application is in enclosures, with a width of 45 mm allowing compact mounting in standard switchboards. The devices are designed for operating temperatures from -40 °C to +70 °C and can be used up to an operating altitude of 2000 m.
Functions and Equipment in Detail
The relay features two changeover contacts as output contacts, suitable for switching operations with a rated current of up to 3 A at AC 230 V. The pickup and dropout values are continuously and independently adjustable, with an adjustment range between 0.7 and 1.3 times the nominal voltage. The hysteresis is less than 4 % of the nominal value, ensuring precise and reliable switching function. The time delay is adjustable between 1 and 20 seconds, enabling a delayed response to short-term voltage fluctuations. The pickup delay is activated to avoid unwanted switching operations during transient voltage changes.
Technology Explained Simply
Measurement is performed via an integrated voltage detection unit directly connected to the network to be monitored. The devices are designed for AC 240 V, with the nominal voltage reaching up to AC 400 V. When connected to an AC voltage, a pickup deviation of 11 % occurs relative to the set value, as the devices are calibrated for DC voltage. The immunity to harmonics ensures stable measurement even with distorted voltage waveforms. The LED indicators signal operational readiness (upper LED) and activation of the output relay (lower LED), allowing visual verification of the operating status.
Compatibility and Accessories
The relay is designed for use in single-phase networks and complies with the standard IEC/EN 60255-1. The terminals are designed according to DIN 46228-1/-2/-3/-4 and allow connection to solid conductors up to 2.5 mm² or stranded conductors up to 1.5 mm². Terminal marking follows EN 50005. The devices are intended for mounting in enclosures and meet the protection rating IP 40 for the housing and IP 20 for the terminals. EMC requirements are met according to IEC/EN 61000-4-2 to -6, including immunity to electrostatic discharge, high-frequency radiation, and fast transients.
Mounting and Installation
Mounting is performed in standard switchboards with a width of 45 mm. The terminals are equipped with self-piercing terminal pins to ensure a secure connection. The connection terminals are designed for a maximum conductor cross-section of 2.5 mm² (solid) or 1.5 mm² (stranded). The devices are designed for continuous operation and do not require additional auxiliary voltage. Adjustment of the pickup and dropout values is done via rotary controls on the device, with values adjustable independently.
Advantages in Operation
Using this relay enables preventive maintenance through early detection of voltage anomalies. The integrated time delay prevents unnecessary switching operations during short-term voltage fluctuations. The LED indicators provide visual feedback on the operating status. The devices are robust and designed for industrial environments, with a mechanical life exceeding 30 million switching operations. The electrical life is 500,000 switching operations at 3 A and AC 230 V. The devices are suitable for operating altitudes up to 2000 m and meet the requirements for overvoltage category III up to 300 V and II from 300 V to 400 V.