| Technical data |
| Classification | Thermistor-Motorschutz |
| Enclosure design | Switch cabinet |
| Measuring range max. | > 3 kΩ |
| Output contacts | 1 C/O contact, 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9038 |
| Variant |
| Auxiliary voltage | AC 42 V |
| Contact equipping | 2 changeover contacts |
| Variant | Without thermal reclosing interlock (manual reset function) |
The Thermistor motor protection relay BA9038 from Dold, type BA9038.12AC50/60HZ42V, is an enclosure device for temperature monitoring of electric motors and other machine components. It serves to protect against thermal overloads caused by high switching frequency, heavy start-up, single-phase operation, impaired cooling, or high ambient temperature. The device class is classified as thermistor motor protection and complies with the standard IEC/EN 60947-8. The auxiliary voltage is AC 42 V, and the width is 45 mm, making it suitable for standard enclosure mounting.
Applications
This relay is primarily used for monitoring the winding temperature of electric motors to prevent thermal damage. It can also be used for temperature monitoring of bearings, gearboxes, oils, and coolants. The application is in industrial plants where reliable and automatic response to overheating is required. The maximum number of connected thermistors is six, which can be connected in series.
Functions and equipment in detail
The device features two changeover contacts as output contacts, enabling flexible integration into existing control and switching circuits. Monitoring is performed via an input to which up to six thermistors (PTC resistors) can be connected. The pickup value is at least 3 kΩ, and the drop-out value is at most 1.8 kΩ. The pickup delay is maximum 20 ms, and the drop-out delay is maximum 15 ms. The function is based on the zero-current principle, in which the output relay is not activated in the event of a fault. A wire break detection in the sensor circuit ensures that a broken sensor wire is detected to avoid false alarms.
Technology explained simply
The relay operates with a PTC resistor (positive temperature coefficient resistor), which increases its resistance as temperature rises. When the resistance reaches the pickup value of 3 kΩ, the output relay drops out and the contacts open. This triggers a motor shutdown or a warning signal. The reset function occurs when the resistance falls below 1.8 kΩ.
Compatibility and accessories
The device is designed for an auxiliary voltage of AC 42 V and can be mounted in enclosures. It is compatible with special PTC resistors designed for motor protection. The variant BA9038.12AC50/60HZ42V is supplied without a reset lock (reset function). Alternative variants with thermal or electromechanical reset lock are available, but are not part of this version. The version with reset lock features a reset button on the front panel, which must be manually operated after activation to return the device to operation.
Mounting and installation
Mounting is done in an enclosure. The terminal designation is standardized: A1/A2 for auxiliary voltage, P1/P2 for the measurement input, and contacts 11-14 and 21-24 for the output relays. The connection terminals are designed for secure connections. Wiring of the thermistors must be done carefully to avoid interference from external voltages. The supply line should be routed separately or shielded, with the shielding grounded at only one end.
Advantages in operation
Reliable temperature monitoring enables preventive shutdown in case of overheating, extending the service life of motors and other machine components. The integrated wire break detection prevents false alarms when sensors are defective. The zero-current principle ensures that the relay is not activated in the event of a fault, increasing safety. The version with two changeover contacts offers flexibility in integration into existing control systems. The width of 45 mm allows compact mounting in standard enclosures.