Dold 0034055, EAN: 4030641340551

Dold 0034055 BA9043 3/N AC50-400Hz 63,5/110V undervoltage relay

Dold 0034055 BA9043 3/N AC50-400Hz 63,5/110V undervoltage relay

Lieske Part No. 1153813
Mfg Part No 0034055
EAN-Code 4030641340551
Manufacturer Dold
Here only 262,20 EUR
312,02 EUR incl. VAT

Further information for Dold 0034055 BA9043 3/N AC50-400Hz 63,5/110V undervoltage relay

Technical data
1- / 3-phase3
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.3/N AC 690 / 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9043
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3/N 63,5/110 V
Time delaywithout
Approvals and MarkingsUKCA, CCC
VariantFor 3p4w systems
The under-voltage relay BA 9043 from Dold is a 3-phase monitoring device for AC networks with neutral conductor. It is designed for continuous monitoring of network voltage and responds to under-voltage conditions by switching the output contacts. The device settings are adjusted via rotary potentiometers on the front panel, enabling user-friendly and precise adjustment of the pickup and dropout values. The device is rated for nominal voltages of 3/N AC 63.5/110 V and can be used in networks with frequencies from 50 to 400 Hz. Measurement is performed via arithmetic mean value calculation, where each phase is measured against the neutral conductor.

Applications
This relay is designed for use in industrial and railway applications, where reliable voltage monitoring is critical for the operational safety of machines and systems. It is particularly suitable for systems requiring continuous power supply and enables preventive maintenance through early detection of voltage drops. The device is installed in enclosures, with a width of 45 mm allowing compact mounting on DIN rail.

Functions and Features in Detail
The device features two changeover contacts as output contacts, used for switching operations in control and protection circuits. The pickup values are continuously adjustable between 0.85 and 1.05 times the nominal voltage, with the dropout value (hysteresis) ranging from 0.75 to 0.95 of the pickup value. LED indicators signal operational readiness (red LED) and activation of the output relay (green LED). The zero-current principle ensures that the output relay is not activated in the event of a fault, enhancing safety. The device is insensitive to harmonics, making it suitable for networks with harmonic distortions.

Technology Explained Simply
The arithmetic mean value measurement enables precise voltage detection in a 3-phase system by measuring the voltage of each phase against the neutral conductor and averaging the values. Adjustment is made via two rotary knobs on the front, allowing the operator to individually set the pickup value and hysteresis according to the requirements of the system. The maximum overload capacity is 1.2 times nominal voltage continuously, and the nominal power consumption is 4 VA. The operating temperature range extends from -20 °C to +60 °C, enabling use in various environments.

Compatibility and Accessories
The relay is designed for 3-phase networks with neutral conductor and complies with the standard IEC/EN 60255-1. It is available for nominal voltages from 3/N AC 100/57 V to 690/400 V, with the variant described here rated for 63.5/110 V. The devices are suitable for frequencies from 50 to 400 Hz. In this variant, no switching delay is provided; however, in other variants (e.g. BA 9043/002), an adjustable time delay of 0.5 to 10 seconds is possible. The contacts are rated for a thermal current of up to 6 A per contact and comply with switching capacities according to AC 15 and DC 13.

Mounting and Installation
Mounting is on DIN rail within an enclosure. The connection terminals are designed for 2 x 2.5 mm² rigid or 2 x 1.5 mm² flexible conductors with heat-shrink tubing. Fixing is achieved using M3.5 plus-minus screws with self-locking clamp levers. The terminal markings are L1, L2, L3 and N for the network to be monitored, and 11, 12, 14 and 21, 22, 24 for the two changeover contacts. Mounting is performed with a torque of 0.8 Nm.

Operational Advantages
The relay enables rapid fault localization and contributes to higher productivity by warning of impending system failures. Preventive maintenance is supported, as voltage drops are detected early. The LED indicators provide a quick visual overview of the operational status. The robust construction, with a mechanical life expectancy of over 30 million switching operations and an electrical life expectancy of 200,000 switching operations at 3 A/AC 230 V, ensures long-term service life. Electromagnetic compatibility according to IEC/EN 61000-4-2 to -4-5 ensures reliable operation even in electromagnetically demanding environments.