| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 72 mm |
| Type | EF 7666 |
| Variant |
| Contact equipping | 1 NO contact undelayed, 1 NO contact delayed, 1 NC contact undelayed, 1 NC contact delayed |
| Nominal voltage | AC 110 V |
| Time range | 0,15 - 1000 s |
The Dold time relay EF7666.24 is a delayed-release industrial time relay for front panel mounting, designed for a rated voltage of AC 110 V and a frequency of 50/60 Hz. It is used for time-delayed control of electrical system components, particularly to account for coast-down behavior, as occurs with motors or other mechanical systems. The delay time is continuously adjustable in the range of 0.15 to 1000 seconds, with six switchable time ranges selectable via a rotary switch on the front. The time function operates on the principle of delayed release with control signal, in accordance with standard EN 61812-1. The time progression is indicated visually, facilitating monitoring of the operating state.
Applications
This device is designed for industrial applications requiring precise time-controlled switching off. Typical uses include controlling fans, pumps, motors, or lighting systems, where immediate switching off after the control signal is not desired. The zero-voltage safety ensures that the relay remains in its output position in the event of a voltage drop, which is important for the safety and stability of control systems.
Functions and Equipment in Detail
The time relay features contact configuration with one instantaneous closer, one delayed closer, one instantaneous opener, and one delayed opener, totaling a changeover contact. The contacts are made of AgNi with a gold plating layer of 0.2 μm, ensuring high switching capacity and long service life. The actuation time of the contacts is less than 35 ms, and the release time is less than 60 ms. The repeatability accuracy is ≤ ± 0.5 % of the scale end value, with an allowable deviation of ≤ ± 1 % in the range of 3 and 6 seconds. The switching position indicator allows visual control of the contact position, which is available in the EF 7666 variant.
Technology Explained Simply
The time progression is implemented mechanically via a clockwork principle, driven by the energy of the input voltage. The delay time is set via a continuously adjustable rotary switch on the front, positioned on an absolute scale. The time ranges are switchable, allowing the user to choose between different time intervals according to requirements. The front of the device is protected against spray water and meets protection class IP 65, enabling use in outdoor or damp environments. The width is 72 mm, allowing installation in standard control panels.
Compatibility and Accessories
The device is designed for a rated voltage of AC 110 V and can be operated within a voltage range of 0.8 to 1.1 times the rated voltage. The frequency is switchable for 50/60 Hz. The contact load capacity is up to 3 A at AC 230 V according to AC 15. The electrical service life is 1 x 10⁵ switching operations at 3 A and 5 x 10⁵ at 1 A. The mechanical service life exceeds 30 x 10⁶ switching operations or 15,000 operating hours. The maximum fuse rating is 10 A gG/gL. Devices in the MINITIMER series, such as AA 7666, EC 7666, and EH 7666, are available in various widths and configurations, with the EF 7666 variant featuring a front surface of 72 x 72 mm.
Mounting and Installation
The device is mounted as a front panel insert in enclosures or control systems. The connection terminals are designed for wiring, with terminal markings A1/A2 for the operating voltage and B1/B2 for the control signal. The delay time is adjusted via the front-mounted rotary switch, which allows switching between time ranges. Mounting requires no additional tools, as the width of 72 mm is standard in control panels.
Advantages in Operation
The combination of wide adjustment range, high repeatability accuracy, and mechanical reliability makes the device suitable for demanding industrial applications. Front-side adjustment and visual indication of switching position simplify commissioning and maintenance. The IP 65 protection class enables robust use in harsh environments. Zero-voltage safety ensures secure switching off in case of failure. The contact configuration with four contacts (two delayed, two instantaneous) offers flexibility in circuit configuration.