| Technical data |
| Enclosure design | Distribution board |
| Output contacts | 1 C/O contact |
| Time function(s) | On-delay |
| Width | 17,5 mm |
| Type | IK 7813 |
| Variant |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC 220 - 240 V |
| Time range | 6 - 60 min |
The Dold time relay IK7813.81 AC220-240V 6-60M is an on-delay relay for industrial and installation control applications. It is used for time-delayed activation of switching operations, where the output contact only switches after a set delay time. The device is designed for a rated voltage of AC 220 to 240 V and features a contact configuration with one changeover contact. The delay time can be adjusted continuously within a range of 6 to 60 minutes, with a repeatability accuracy of ≤ 1 %. The width of 17.5 mm allows for compact mounting in standard installation distributors according to DIN 43880. The housing design is intended for installation distributors, with connection terminals located at the bottom. The operating voltage range is 0.8 to 1.1 times the rated voltage, ensuring stable operation even with voltage fluctuations. The drop-out voltage is 15 % of the rated voltage, ensuring the relay switches off safely when the supply voltage falls below this value.
Applications
This relay is suitable for applications in industrial automation and electrical installation where time-delayed switching operations are required. Examples include delay during motor start-up, time-controlled activation of lighting systems, or control of pumps and heating systems. The high repeatability accuracy and continuous adjustability of the delay time enable precise and reproducible processes. The operating temperature ranges from -20 °C to +60 °C, allowing use in indoor environments and industrial settings with moderate temperatures. The relative humidity may reach up to 95 % at 40 °C, enabling use in humid environments.
Functions and Features in Detail
The relay includes an LED indicator showing the contact position. The LED lights up when the output contact (15-18) is closed, i.e., when the relay is activated. The time delay is on-delay, meaning the contact only switches after the set time has elapsed. The time setting is adjusted continuously on a relative scale, allowing precise adaptation to the specific application. Changing the time setting during the timing process is immediately applied, which may cause the output relay to activate unintentionally. The reset time is less than 60 ms at 50/100 Hz, enabling rapid reset after switching off the input voltage.
Technology Explained Simply
The relay technology is based on an electronic timing circuit that generates the delay time via an internal timer. The input voltage is supplied via terminals A1/A2, with a rated voltage of AC 220–240 V. The output contacts (15, 16, 18) are configured as a changeover contact, with contact 15-18 closing when the relay is activated. The contact materials consist of AgSnO₂, ensuring high switching durability and good contact quality. The rated operating voltage for the outputs is AC 250 V, and the contact drop-out time is less than 20 ms. The thermal current rating (Ith) is up to 10 A, with the total current limit curve defining the maximum permissible load. The electrical life is at least 500,000 switching operations at 3 A and AC 230 V, while the mechanical life exceeds 30 million switching operations.
Compatibility and Accessories
The relay is designed for use in installation distributors according to DIN 43880 and can be installed in enclosures with mounting plates and cable ducts. It is compatible with other devices from the IK 7813 and SK 7813 series, with the latter featuring a greater depth (98 mm) and top-mounted connection terminals. The switching capacity complies with IEC/EN 60947-5-1, with the make contact capable of switching up to 10 A at AC 230 V and the break contact up to 5 A. The incandescent lamp load is 1200 W, enabling use in lighting installations. The permissible switching frequency is 6000 switching operations per hour, indicating high operational load capacity.
Mounting and Installation
Mounting is performed in standard installation distributors with a width of 17.5 mm. The connection terminals are located at the bottom, enabling easy wiring. The depth is 58 mm, allowing installation in distributors with sufficient space. Mounting is done via the integrated plug-in strip, which is inserted into the corresponding mounting sockets. The connection terminals are designed for cable connections, with the maximum permissible current load limited by the thermal current rating of 10 A. The housing protection rating is IP 40, protecting against finger contact and ingress of solid foreign objects larger than 1 mm. The terminals themselves have a protection rating of IP 20.
Operational Advantages
The relay offers high precision through repeatability accuracy of ≤ 1 % and continuous adjustability of the delay time. The LED indicator enables visual monitoring of the operating status. The robust construction, with a mechanical life exceeding 30 million switching operations and an electrical life of 500,000 switching operations at 3 A, ensures long service life. Compliance with standard EN 61812-1 guarantees safe and reliable operation. The operating temperature range of -20 to +60 °C and high humidity tolerance of 95 % at 40 °C extend the application range to various environments. The switching capacity and thermal load capacity make the relay suitable for a wide range of industrial and installation applications.