| Technical data |
| Enclosure design | Distribution board |
| Output contacts | 1 C/O contact |
| Time function(s) | Fleeting on make |
| Width | 17,5 mm |
| Type | IK 7815 |
| Variant |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC/DC 24 V |
| Time range | 0,1 - 1 s |
| Variant | Fleeting action |
The Dold IK7815.71 AC/DC24V 0,1-1S is an
on-delay latching relay of the IK 7815 series, designed for time-dependent control applications in industrial and installation environments. The device features a
17.5 mm mounting width and is designed for installation in installation distributors according to DIN 43880, with connection terminals arranged at the bottom. It is used for time-delayed switching of loads, where the contact remains closed for an adjustable time range of 0.1 to 1 second after the relay is energized. The function is defined as
on-delay latching, meaning the contact remains activated for the set time after voltage is applied and then returns to its default state.
Applications
This relay is suitable for applications requiring time-delayed activation of switching operations, such as in lighting systems, pump controls, heating systems, or for synchronizing machine components. The
repeatability of ≤ ±1 % ensures high precision in repeated switching operations, which is important for automated processes. The
LED indicator signals the state of the output relay – illuminated when contact 15-18 is closed, i.e., activated.
Functions and Equipment in Detail
The device features
1 changeover contact as its contact configuration, enabling it to open one circuit and close another. The
latching time is continuously adjustable and can be set directly on the device via a relative scale. Any change to the time setting takes effect immediately. The
reset time is less than 60 ms for models 50/100, enabling a quick response after de-energizing. The
rated voltage is AC/DC 24 V, with an operating voltage range between 0.8 and 1.1 times the rated voltage. For battery operation, the range is 0.9 to 1.25 times the rated voltage.
Technology Explained Simply
The relay operates on the principle of an
on-delay latching relay, where the contact remains activated for the set time after the input voltage is applied. The time delay is generated by an internal timing mechanism that operates independently of the mains voltage. The
voltage influence is ≤ 1 % within the range of 0.8 to 1.1 times the rated voltage, ensuring stable operation even with voltage fluctuations. The
temperature dependence is 0.05 % per Kelvin, indicating low sensitivity to ambient temperature changes. The
rated power consumption is 0.6 W at AC/DC 24 V.
Compatibility and Accessories
The device is designed for use in
installation distributors according to DIN 43880. It is available in two versions: the IK 7815 variant with a mounting depth of 58 mm and terminals at the bottom, and the SK 7815 variant with a mounting depth of 98 mm and terminals at the top for enclosures. The
switching capacity complies with IEC/EN 60947-5-1: as a make contact (AC 15) up to 10 A at AC 230 V, and as a break contact up to 5 A at AC 230 V. The
rated operational voltage is AC 250 V. The
mechanical life expectancy exceeds 30 million switching operations, and the
electrical life expectancy is 500,000 switching operations at 3 A and AC 230 V.
Mounting and Installation
The relay is installed in standard installation distributors with a mounting width of 17.5 mm. The terminals are located at the bottom, enabling easy wiring. Mounting is carried out in the usual manner in DIN distributors, taking into account the mounting depth of 58 mm. The
operating temperature ranges from -20 °C to +60 °C, and the
storage temperature ranges from -25 °C to +70 °C. The
relative humidity must not exceed 95 % at 40 °C. The
operating altitude is limited to below 2000 m.
Advantages in Operation
The
continuous adjustability of the latching time allows flexible adaptation to different requirements. The
high repeatability ensures reliable and reproducible switching operations. The
LED indicator provides visual feedback on the relay’s status. The
short-circuit resistance is ensured by a maximum fuse rating of 10 A gG/gL or a circuit breaker with B16 tripping characteristic. The
protection rating IP 40 for the housing and IP 20 for the terminals protects against contact and foreign objects, but not against splashing water or dust. The
EMC testing according to IEC/EN 61000-4-2 to -4-6 ensures good immunity to electromagnetic interference. The device complies with the standard
IEC/EN 61812-1 for time relays.