Dold 0033210, EAN: 4030641332105

Dold 0033210 IK7814.81 time relay delayed-on

Dold 0033210 IK7814.81 time relay delayed-on

Lieske Part No. 1153872
Mfg Part No 0033210
EAN-Code 4030641332105
Manufacturer Dold
Here only 123,49 EUR
146,95 EUR incl. VAT

Further information for Dold 0033210 IK7814.81 time relay delayed-on

Technical data
Enclosure designDistribution board
Output contacts1 C/O contact
Time function(s)On-delay
Width17,5 mm
TypeIK 7814
Variant
Contact equipping1 changeover contact
Nominal voltageAC 220 - 240 V
Time range0,25 - 640 min
Variant4 time ranges can be programmed via the terminals
The Dold IK7814.81 is a delayed-on time relay, specifically designed for industrial and installation control applications. It enables time-controlled activation of switching operations, with the output contact closing only after the set delay time has elapsed. The device complies with standard EN 61812-1 and is designed for use in installation distributors according to DIN 43880. The width is 17.5 mm, allowing compact mounting in standard distributors. The rated voltage is AC 220–240 V, and the time delay can be continuously adjusted in the range of 0.25 to 640 minutes. The time function is delayed-on, meaning the contact closes only after the control voltage is switched on and the set time has elapsed.

Applications
This time relay is suitable for applications requiring a time-delayed switching function, such as lighting controls, pump regulation, heating systems, or machine process control. The high repeatability of ≤ 1 % ensures reliable and precise time control. The LED indicator signals the state of the output relay – illuminated when the contact 15–18 is closed. This facilitates diagnosis and maintenance during operation.

Functions and Equipment in Detail
The device features a changeover contact as the output contact, consisting of a close contact (15–18) and an open contact (15–16). The contact materials are made of AgSnO₂, ensuring high switching durability and corrosion resistance. The switching capacity is up to 10 A at AC 230 V for the close contact and 5 A for the open contact, according to AC 15 per IEC/EN 60947-5-1. The electrical life is 500,000 switching operations at 3 A and AC 230 V. The mechanical life exceeds 30 million switching operations, indicating high robustness. The reset time is less than 60 ms at 50/100 Hz, enabling a quick response after switching off.

Technology Explained Simply
The time delay is programmed externally via three control inputs (Z3, Z4, Z5). By using different bridging connections between these terminals, four time ranges can be selected: 0.25–2.5 s, 1–10 s, 8–80 s, and 64–640 s (or 0.25–2.5 min, 1–10 min, 8–80 min, 6–640 min). Adjustment is continuous on a relative scale. Terminals Z3, Z4, Z5 are not galvanically isolated from connection terminals A1/A2, which must be considered during installation. Voltage influence values are ≤ 1 % at 0.8–1.1 times rated voltage, and temperature influence is 0.05 % per Kelvin. The dropout voltage is 15 % of the rated voltage.

Compatibility and Accessories
The device is available in two housing types: IK 7814 with 58 mm depth and bottom-mounted terminals for installation distributors, and SK 7814 with 98 mm depth and top-mounted terminals for enclosures with mounting plate and cable duct. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +70 °C. Relative humidity is up to 95 % at 40 °C. The operating altitude is limited to ≤ 2000 m. The insulation test voltage is 2.5 kV for a duration of 1 minute. The overvoltage category is III, and the rated impulse withstand voltage is 4 kV at pollution degree 2.

Mounting and Installation
Mounting is performed in standard installation distributors according to DIN 43880. The connection terminals are arranged at the bottom, enabling easy integration into existing control systems. Terminals A1/A2 serve as the input for the control voltage, while Z3, Z4, Z5 are used for programming the time ranges. Terminals 15, 16, 18 are the output contacts of the changeover. The maximum fuse rating is 10 A gG/gL, and the maximum circuit breaker tripping characteristic is B16. The permissible switching frequency is 6000 switching operations per hour.

Advantages in Operation
The time relay offers high precision and reliability due to repeatability of ≤ 1 % and long service life. The LED indicator allows for quick visual monitoring of the operating status. The flexible time programming via terminals Z3–Z5 enables adaptation to different requirements without mechanical modifications to the device. Compliance with standard EN 61812-1 and EMC tests according to IEC/EN 61000-4-2 to -4-6 ensures safe and interference-free operation in industrial environments. Radio frequency interference suppression meets limit class B according to EN 55011.