Dold 0032255, EAN: 4030641322557

Dold 0032255 under-voltage relay 0.5-10 s

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0032255 under-voltage relay 0.5-10 s

Lieske Part No. 505540
Mfg Part No 0032255
EAN-Code 4030641322557
Manufacturer Dold
Here only 302,01 EUR
359,39 EUR incl. VAT

Further information for Dold 0032255 under-voltage relay 0.5-10 s

Technical data
1- / 3-phase3
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.3/N AC 690 / 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9043
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3/N 63,5/110 V
Time delay0,5 - 10 s
Approvals and MarkingsUKCA, CCC
VariantFor 3p4w systems. With adjustable time delay
The Dold undervoltage relay BA9043/002 is a 3-phase monitoring device for AC power networks with neutral conductor, designed for nominal voltages of 3/N AC 63.5/110 V. It is used for continuous monitoring of the network voltage and de-energizes output contacts in case of undervoltage, protecting connected devices from damage. The device operates on the rest current principle, in which the output relay is not activated in the event of a fault, ensuring safe and reliable operation. Adjustment is performed via rotary potentiometers on the front of the device, allowing user-friendly and precise setting of pickup and dropout values.

Applications
This relay is designed for industrial applications as well as railway applications, where stable and reliable power supply is critical. It monitors 3-phase AC networks in the frequency range of 50 to 400 Hz and is suitable for operating altitudes up to 2000 m. The arithmetic mean value measurement enables precise voltage detection, with each phase measured against the neutral conductor. Insensitivity to harmonics ensures robust operation even in networks with harmonic distortions.

Functions and Equipment in Detail
The device features two changeover contacts as output contacts, designed for switching operations with a thermal current of up to 6 A per contact. The switching delay is continuously adjustable in the range of 0.5 to 10 seconds, with the delay only effective at voltages above 0.6 times nominal voltage. Below 0.4 times nominal voltage, dropout occurs immediately. LED indicators signal operational readiness (red LED) and contact position (green LED), simplifying fault localization.

Technology Explained Simply
The pickup values are continuously adjustable in the range of 0.85 to 1.05 times nominal voltage, with the dropout ratio (hysteresis) ranging between 0.75 and 0.95 of the pickup value. The nominal frequency is 50 to 400 Hz, and the temperature dependence of measurement is less than 0.05 % per Kelvin. The device is compliant with IEC/EN 60255-1 and designed for continuous operation.

Compatibility and Accessories
The relay is available for networks with or without neutral conductor, with the BA9043/002 variant specifically designed for systems with neutral conductor. It is suitable for nominal voltages from 3/N AC 100/57 V to 690/400 V. The width is 45 mm, enabling mounting on DIN rail. The electrical life is at least 200,000 switching operations at 3 A and AC 230 V, while the mechanical life exceeds 30 million switching operations.

Mounting and Installation
Mounting is on DIN rail in accordance with IEC/EN 60715. The connection terminals are designed for 2 x 2.5 mm² rigid or 2 x 1.5 mm² flexible conductors with shrink tubing. Dimensions are 45 mm (width) × 73 mm (height) × 132 mm (depth). Fixing is done using M3.5 plus-minus screws with self-locking clamp lever, with a torque of 0.8 Nm. The operating temperature range is -20 °C to +60 °C, and the storage temperature range is -25 °C to +60 °C.

Advantages in Operation
Preventive maintenance is supported by clear indication of operating states and easy parameter adjustment. Rapid fault localization is enabled by LED indicators and clear signaling of contact position. High service life and robustness against environmental influences such as vibrations and shock loads (Category 1, Class B according to IEC/EN 61373) ensure reliable performance in demanding environments. EMC immunity against static discharges (8 kV), HF radiation (20 V/m), and fast transients (2 kV) guarantees stable operation even in electromagnetically stressed environments.