Further information for Dold 0031015 voltage relay BA9036 AC50Hz 24V
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
AC 24 V 50 Hz
Time delay
without
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation
The Dold voltage relay BA9036 AC50HZ 24V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks in industrial applications. It operates on the principle of residual current and is designed for mounting in enclosures. The device settings are adjusted via rotary switches on the front, ensuring simple and user-friendly configuration. The relay enables early detection of voltage drops or irregularities to prevent electrical system failures and enhance operational safety.
Applications
This relay is suitable for monitoring voltages in the range of 24 to 400 V AC. It is used in industrial installations where continuous voltage monitoring is required to ensure the functionality of critical equipment and machinery. The device is installed in enclosures, integrated via standard rail mounting with a width of 45 mm. It is designed for use in environments where the operating temperature ranges from -20 °C to +60 °C.
Functions and Equipment in Detail
The BA9036 features two changeover contacts as output contacts, rated for switching operations with a thermal current (Ith) of 6 A. The switching capacity is 2 A at AC 230 V (AC 15) for make contacts and 1 A at AC 230 V for break contacts. For DC, the switching capacity is 1 A at DC 24 V (DC 13). The electrical life is 1.5 × 10⁵ switching operations at 6 A and AC 230 V, while the mechanical life is 30 × 10⁶ switching operations. The pickup delay is adjustable and ranges from 0.5 to 10 seconds, with the delay only active when the voltage exceeds 60 % of the nominal voltage. The adjustment range is between 0.85 and 1.05 of the nominal voltage, with variant /1_ providing a range of 0.9 to 1.25 of the nominal voltage. The dropout ratio (hysteresis) is 0.75 to 0.95 of the set value, ensuring stable switching behavior during voltage fluctuations.
Technology Explained Simply
The relay monitors the applied voltage and responds when it falls below the set pickup value. In case of undervoltage, it switches the output contacts, which can trigger an alarm or shutdown, for example. The dropout voltage is lower than the pickup value to avoid switching during brief voltage fluctuations. The LED indicators show operational readiness (upper LED) and the activated contact position (lower LED). The device requires no auxiliary voltage, as it is powered directly from the monitored voltage source. The nominal voltage is AC 24 V at 50 Hz, with a maximum nominal voltage of AC 400 V. Frequency deviation is limited to ±5 %, and the temperature influence on measurement accuracy is less than 0.05 % per Kelvin.
Compatibility and Accessories
The relay is designed for use in single-phase networks and complies with the standard IEC/EN 60255-1. For DC voltages above 60 V, an external series resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. Required series resistors are available as accessories, for example ZWS 20 SL 1.5 kΩ 20 W for DC 110 V. The terminals are designed such that only the intended series resistor may be connected to terminal z.
Mounting and Installation
The device is mounted in enclosures and is designed for installation on 35 mm rails. The width is 45 mm, enabling compact placement in standard control systems. The connection terminals are designed for wiring, with terminals e, f, and z designated for voltage monitoring and the external series resistor. Installation requires no additional tools, as the device is designed for standard rail mounting.
Operational Advantages
By enabling early detection of voltage drops, the relay allows for preventive maintenance and reduces the likelihood of machine downtime. The adjustable pickup and dropout values, as well as the pickup delay, allow application-specific customization. The LED indicators provide visual feedback on the operational status, accelerating fault localization. The high mechanical and electrical life ensures reliable long-term use in industrial environments. The device operates without auxiliary voltage, simplifying installation and reducing dependence on additional power supplies.