Further information for Dold 0030438 voltage relay BA9036 DC220V
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
DC 220 V
Time delay
without
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation
The voltage relay BA 9036 from Dold is an undervoltage relay for monitoring single-phase DC and AC power networks. It is designed for continuous monitoring of the supply voltage to detect voltage dips or failures early, thereby increasing the operational safety of electrical installations. The device operates on the standby current principle, where the contacts are closed during normal operation and open in case of undervoltage. Adjustment is performed via rotary switches on the front panel, enabling user-friendly and precise setting of the pickup and dropout values. The devices are designed for use in enclosures and have a width of 45 mm, making them suitable for standard control panels.
Applications
This relay is designed for industrial and technical applications where reliable voltage monitoring is required. Examples include drive technology, pump control systems, lighting systems, or safety functions in production plants. The ability to monitor both DC and AC voltages expands its range of applications. Monitoring is performed in the range of 24 to 400 V, with the nominal voltage for this variant being DC 220 V. The maximum nominal voltage is AC 400 V.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used for switching operations in control and protection circuits. The contacts are rated for a thermal current of 6 A and meet switching capacities according to AC 15 (make: 2 A / AC 230 V, break: 1 A / AC 230 V) and DC 13 (make: 1 A / DC 24 V, break: 1 A / DC 24 V). The electrical life is 150,000 switching operations at 6 A and AC 230 V, while the mechanical life is 30 million switching operations. The dropout hysteresis is between 0.75 and 0.95 of the set value, ensuring stable and bounce-free operation. The pickup delay is adjustable and ranges from 0.5 to 10 seconds, but is only active when the voltage is above 60 % of the nominal voltage.
Technology Explained Simply
The relay monitors the applied voltage and reacts when it falls below the set pickup value. In case of undervoltage, the contacts open, triggering for example a shutdown or alarm. Adjustment is done via rotary switches that precisely define the pickup and dropout values. The LED indicators show operational readiness (upper LED) and activation of the output relay (lower LED). For DC voltages above 60 V, an external series resistor is required, connected to terminals e and z. For DC 220 V, the series resistor ZWS 35 SL with 3.9 kΩ and 35 W is specified. The device operates without auxiliary voltage, simplifying installation and ensuring independence from additional power supplies.
Compatibility and Accessories
The relay is designed for use in enclosures and complies with the standard IEC/EN 60255-1. Accessories required for operation at higher DC voltages include external series resistors specifically designed for the respective voltage. For DC 220 V, the series resistor ZWS 35 SL is specified. The devices are designed for an operating temperature range of -20 to +60 °C and can be used in indoor and outdoor installations, provided the environmental conditions are within the specified limits.
Mounting and Installation
Mounting is performed in standard control panels with a width of 45 mm. Connections are made via terminals, with the measured voltage connected to e and f. The external series resistor, if required, is connected to e and z. Terminal z is exclusively intended for the series resistor. Installation requires adherence to safety instructions, particularly regarding the shock protection of the series resistor, which becomes very hot during operation.
Advantages in Operation
Early detection of voltage dips enables preventive maintenance and reduces downtime. The clear LED indication facilitates diagnosis and fault localization. The adjustable pickup and dropout values, as well as the pickup delay, allow application-specific adaptation. Operational safety is enhanced by the high life expectancy and reliability of the contacts. The device is designed for industrial environments and meets requirements for reliability and safety.
Approvals and Markings
The device carries the CCC approval, confirming compliance with applicable safety and quality standards. Compliance with the standard IEC/EN 60255-1 ensures reliability and interoperability in industrial control systems.