Dold 0030261, EAN: 4030641302610

Dold 0030261 thermistor motor protection relay BA9038.11/003 110V

Dold 0030261 thermistor motor protection relay BA9038.11/003 110V

Lieske Part No. 1153677
Mfg Part No 0030261
EAN-Code 4030641302610
Manufacturer Dold
Here only 170,24 EUR
202,59 EUR incl. VAT

Further information for Dold 0030261 thermistor motor protection relay BA9038.11/003 110V

Technical data
ClassificationThermistor-Motorschutz
Enclosure designSwitch cabinet
Measuring range max.> 3 kΩ
Output contacts1 C/O contact, 2 C/O contacts
Width45 mm
TypeBA 9038
Variant
Auxiliary voltageAC 110 V
Contact equipping1 changeover contact
VariantWith thermal magnetic reclosing interlock (manual reset function)
The Thermistor motor protection relay BA 9038 from Dold is a protection device for electric motors designed to prevent thermal overloads. It is used to protect motors from damage caused by high switching frequency, heavy start-up, single-phasing, impaired cooling, or high ambient temperature. Additionally, it can be used for temperature monitoring of bearings, gearboxes, oils, and coolants. The device operates on the rest current principle, in which the output relay is not activated in the event of a fault, and monitors the sensor circuit for wire breakage. The BA9038.11/003 variant features a thermal-mechanical re-energizing lockout, which maintains the output relay state after tripping due to reaching the tripping temperature, even if the temperature drops again. The lockout is voltage failure-safe, meaning it retains its state even during power failure. To restore operational readiness, the button on the front of the device must be pressed.

Applications
This relay is designed for use in enclosures and is suitable for industrial applications where reliable temperature monitoring of motors is required. It can also be used to monitor other thermally stressed components such as bearings or gearboxes. Applications occur in environments where motors are at risk due to high loads, poor cooling, or high ambient temperatures. The connecting wires from the thermistor to terminals P1 and P2 must not be influenced by external voltages and should therefore be routed in a separate cable. The total resistance of the wiring must not exceed 100 Ω.

Functions and Equipment in Detail
The device has one input to which up to six thermistors (PTC resistors) can be connected in series. The actuation value is at a resistance of at least 3 kΩ, and the reset value is at most 1.8 kΩ. The actuation delay is maximum 20 ms, and the reset delay is maximum 15 ms. The auxiliary voltage is AC 110 V, and the nominal frequency is 50/60 Hz. The contact configuration is 1 changeover contact. The BA9038.11/003 version does not include an indicator LED. The re-energizing lockout is activated by a button on the front, which pops out after tripping. The device complies with IEC/EN 60947-8.

Technology Explained Simply
The relay operates on a rest current principle, where the output relay is activated during normal operation. When the resistance of the thermistor reaches the actuation value of 3 kΩ, the relay drops out and the re-energizing lockout is activated. The lockout remains active even during power failure, ensured by the voltage failure-safe design. Resetting is done by manually pressing the button on the front. Measurement is performed via input P1/P2, with the total wiring resistance limited to prevent false alarms.

Compatibility and Accessories
The device is designed for use with specific PTC resistors (positive temperature coefficient resistors) integrated into motor windings. It is compatible with various auxiliary voltages, including AC 24, 42, 48, 110, 127, 230, and 240 V. The width is 45 mm, making it suitable for standard enclosure mounting. Terminal markings include A1/A2 for auxiliary voltage, P1/P2 for the measurement input, and contacts 11-14 and 21-24 for relay contacts.

Mounting and Installation
Mounting is done in enclosures. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, P1/P2 for measurement input, and 11-14 and 21-24 for relay contacts. The total wiring resistance must not exceed 100 Ω. Installation must follow the instructions in the datasheet, ensuring electrical safety and correct wiring.

Operational Advantages
The BA 9038 provides reliable temperature monitoring and protects motors from thermal overloads. The re-energizing lockout prevents uncontrolled restart of the motor after a tripping event. The voltage failure-safe design ensures the protection status is maintained even during power failure. The simple reset by pressing the button on the front allows for quick restoration of operational status. Compliance with IEC/EN 60947-8 ensures high safety and reliability standards.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1153677
qrcode für Dold 0030261 thermistor motor protection relay BA9038.11/003 110V