| Technical data |
| Classification | Thermistor-Motorschutz |
| Enclosure design | Switch cabinet |
| Measuring range max. | > 3 kΩ |
| Output contacts | 1 C/O contact, 2 C/O contacts |
| Width | 45 mm |
| Type | BA 9038 |
| Variant |
| Auxiliary voltage | AC 110 V |
| Contact equipping | 2 changeover contacts |
| Variant | Without thermal reclosing interlock (manual reset function) |
The Thermistor motor protection relay BA 9038 from Dold is an enclosure device for temperature monitoring of electric motors and other machine components. It serves to prevent thermal overloads that may occur due to high switching frequency, heavy start-up, single-phase operation, impaired cooling, or high ambient temperature. The device monitors up to six series-connected thermistors (PTC resistors) installed in the motor windings and reacts when the resistance value reaches a defined threshold. The BA9038.12 version features two changeover contacts as output contacts and is designed for an auxiliary voltage of AC 110 V. The width is 45 mm, enabling compact mounting in standard enclosures.
Applications
This relay is primarily designed for protecting electric motors, especially in systems operating under high thermal loads. It is also suitable for temperature monitoring of bearings, gearboxes, oils, and coolants. Applications are in industrial environments where reliable monitoring of operating temperature is necessary to prevent damage to machines and systems. The use of up to six thermistors enables comprehensive monitoring of larger motors or multiple components.
Functions and equipment in detail
The device operates on the principle of rest current, where the output relay de-energizes in the event of a fault, ensuring safe disconnection of the affected system. The wire break detection in the sensor circuit ensures that a defective or broken sensor is detected, preventing false alarms or undetected overloads. The pickup value is at least 3 kΩ, and the drop-out value is at most 1.8 kΩ. The pickup delay is limited to a maximum of 20 ms, and the drop-out delay to a maximum of 15 ms, enabling rapid response to temperature changes.
Technology explained simply
The input circuits of the relay are designed for the connecting leads of the thermistors. The total lead resistance must not exceed 100 Ω to ensure accurate measurement. The terminal connections P1 and P2 serve as input for the thermistors, while A1 and A2 supply the auxiliary voltage (AC 110 V). The output contacts (11-14 and 21-24) are configured as changeover contacts and allow control of auxiliary circuits, e.g., for switching off a motor or triggering a warning indicator. The device complies with the standard IEC/EN 60947-8, which applies to motor protection relays.
Compatibility and accessories
The relay is designed for use with special PTC resistors (positive temperature coefficient resistors) developed for motor protection purposes. The number of connected thermistors can range from one to six, all connected in series. The BA9038.12 version is available without a reset lock (no reset function), meaning that after tripping, the device must be manually reset via the front panel and does not reset automatically.
Mounting and installation
Mounting is carried out in an enclosure, with the width of 45 mm enabling standard installation. The terminal connections are clearly labeled (A1/A2 for auxiliary voltage, P1/P2 for input, 11-14 and 21-24 for output contacts). The thermistors are wired via the input terminals P1 and P2. The auxiliary voltage is connected via A1 and A2. The connecting leads should be routed according to technical specifications to avoid measurement errors.
Advantages in operation
The relay provides reliable temperature monitoring, protecting against thermal damage. The integrated wire break detection increases safety by identifying a defective sensor. The fast pickup and drop-out delays enable precise response to temperature changes. Compliance with IEC/EN 60947-8 ensures adherence to international standards. The version without reset lock requires manual reset after tripping, enabling controlled reactivation. The width of 45 mm and enclosure design ensure flexible integration into existing systems.