Further information for Dold 0029327 Undervoltage Relay 415V
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 415 V
Time delay
0,5 - 10 s
Approvals and Markings
UKCA
Variant
For 3p3w systems. With adjustable time delay
The undervoltage relay BA9043/003 from Dold is a 3-phase monitoring device for three-phase AC networks without a neutral conductor. It is designed for continuous monitoring of network voltage and de-energizes output contacts in case of undervoltage, protecting downstream equipment from damage. The device settings are adjusted via rotary potentiometers on the front panel, enabling user-friendly and precise adjustment of pickup and dropout values. The device operates on the standby current principle, where the output relay is not activated in the event of a fault, ensuring safe and reliable signal transmission.
Applications
This relay is designed for use in industrial and railway applications, where reliable voltage monitoring of 3-phase AC networks is required. It is particularly suitable for networks with frequencies between 50 and 400 Hz and is rated for nominal voltages of 3AC 415 V. The maximum nominal voltage is 3/N AC 690 / 400 V, and the device can be operated continuously at up to 1.2 times the nominal voltage. The operating temperature ranges from -20 °C to +60 °C, enabling use in various industrial environments.
Functions and Equipment in Detail
The device monitors voltage via arithmetic mean measurement. For the BA9043/003 variant, designed for networks without a neutral conductor, phases L1 and L2 are measured against L3. Pickup values are continuously adjustable between 0.85 and 1.05 times nominal voltage, with the dropout value (hysteresis) ranging between 0.75 and 0.95 of the pickup value. The time delay is adjustable and ranges from 0.5 to 10 seconds. This delay is only effective if the voltage is at least 0.6 times nominal voltage; below 0.4 times nominal voltage, the output relay de-energizes immediately.
Technology Explained Simply
Power supply is directly from the monitored network. The LED indicators show operational readiness (red LED) and activation of the output relay (green LED). The device is harmonic-insensitive, meaning it operates reliably even in networks with harmonic distortions. The switching delay allows differentiation between short-term voltage dips and sustained interruptions, preventing unwanted shutdowns.
Compatibility and Accessories
The relay is designed for three-phase networks without a neutral conductor and complies with the standard IEC/EN 60255-1. It is intended for use in enclosures and has a width of 45 mm. The connection terminals are designed for connection with solid or stranded conductors according to DIN 46228. Mounting is on a DIN rail in accordance with IEC/EN 60715. The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V, with a mechanical life expectancy exceeding 30 million switching operations.
Mounting and Installation
Mounting is on a DIN rail inside the enclosure. The connection terminals are equipped with plus-minus screws M3.5 with self-lifting clamping rings. The required stripping length is 10 mm, and the tightening torque is 0.8 Nm. The terminals are rated for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded conductors. The device front features two rotary potentiometers for adjusting pickup and dropout values, which can be set directly on the device.
Operational Advantages
Through preventive maintenance and faster fault localization, productivity is increased. The device enables early detection of voltage dips, preventing damage to downstream equipment. The clear LED indication and simple operation via rotary potentiometers ensure high user-friendliness. The harmonic insensitivity and frequency stability up to 400 Hz make the relay suitable for demanding applications in industry and rail transport. Short-circuit resistance is ensured by a maximum fuse rating of 4 A gG / gL, enhancing operational safety.