Further information for Dold 0028766 BA9036 DC60V voltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
DC 60 V
Time delay
without
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation
The Dold voltage relay BA9036 DC60V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC or AC voltage networks in industrial applications. It operates on the principle of residual current and is rated for a nominal voltage of DC 60 V. Device settings are adjusted via rotary switches on the front panel, enabling simple and user-friendly configuration. The relay enables early detection of voltage drops and thus supports preventive maintenance of electrical systems, helping to avoid failures and increase operational safety.
Applications
The relay is intended for use in enclosures and is suitable for monitoring voltage supplies in industrial systems, such as in manufacturing technology, automation technology, or systems with critical power supply. It monitors DC and AC voltages in the range of 24 to 400 V, with the DC60V variant specifically designed for DC networks. Monitoring is continuous, and when the set trigger threshold is undershot, an output relay is activated to trigger a response from the control system or a switch.
Functions and Equipment in Detail
The BA9036 features two changeover contacts as output contacts, rated for switching operations in the range of AC 230 V (2 A make, 1 A break) and DC 24 V (1 A make and break). The trigger thresholds are adjustable within a range of 0.85 to 1.05 times the nominal voltage, with the variant /1_ _ allowing a range of 0.9 to 1.25 times. The reset values (hysteresis) lie between 0.75 and 0.95 of the set trigger threshold, ensuring stable switching behavior without oscillations. Repeatability is ±0.5 %, enabling high precision in voltage monitoring.
Technology Explained Simply
The relay operates without auxiliary voltage, meaning it is directly connected to the voltage source to be monitored. Power supply is provided by the measured voltage itself. The trigger delay is adjustable and ranges from 0.5 to 10 seconds, with this function only active when the voltage exceeds 0.6 times the nominal voltage. This prevents unwanted switching operations during short-term voltage fluctuations. Device indicators consist of two LEDs: the upper LED lights up when operating voltage is present, and the lower LED indicates the state of the output relay.
Compatibility and Accessories
The relay is compliant with IEC/EN 60255-1 and carries the CCC certification. It is designed for use in enclosures and has a width of 45 mm. For variants with DC voltage exceeding 60 V, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. For variants DC 110 V, DC 127 V, DC 220 V, and DC 240 V, specific resistors (e.g., ZWS 20 SL 1.5 kΩ 20 W) are provided as accessories. The maximum overload capacity is 1.2 times the nominal voltage continuously.
Mounting and Installation
The relay is mounted in enclosures and is rated for an operating temperature of -20 to +60 °C. Mounting is done using the designated mounting elements in the enclosure. Connections are made to terminals e, f, and z, with terminal z exclusively intended for the external resistor. The mechanical life is 30 million switching operations, and the electrical life at 6 A and AC 230 V is 150,000 switching operations. Short-circuit resistance is defined by a maximum fuse rating of 4 A gG/gL according to IEC/EN 60947-5-1.
Advantages in Operation
By enabling early detection of voltage drops, the BA9036 allows for proactive maintenance and reduces the likelihood of system downtime. The adjustable trigger and reset thresholds, along with the trigger delay, offer flexibility in adapting to different requirements. The LED indicators facilitate diagnosis and status monitoring during operation. The device is designed for industrial environments and provides high reliability under continuous operation.