Further information for Dold 0028765 BA9036 DC24V voltage relay
Technical data
1- / 3-phase
1
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
AC 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9036
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
DC 24 V
Time delay
without
Approvals and Markings
CCC
Variant
Undervoltage relay. Closed circuit operation
The Dold voltage relay BA9036 DC24V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC or AC voltage networks in industrial applications. It operates on the standby current principle and is designed for mounting in enclosures. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The relay enables early detection of voltage drops or failures, preventing electrical system outages and enhancing operational safety.
Applications
This relay is suitable for monitoring voltages in the range of 24 to 400 V, with the nominal voltage for this variant being DC 24 V. It is used in industrial installations requiring continuous voltage monitoring, such as automation systems, machine controls, or installations with critical power supply. The single-phase design makes it particularly suitable for applications where a single voltage source needs to be monitored.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or signal indicators. The pickup and drop-out values are adjustable, with the adjustment range between 0.85 and 1.05 times the nominal voltage. For the variant /1_ _, the adjustment range is 0.9 to 1.25 times the nominal voltage. The hysteresis, i.e., the difference between pickup and drop-out value, is between 0.75 and 0.95 of the set value. The repeatability accuracy is ± 0.5 %, ensuring high precision in voltage monitoring. The pickup delay is adjustable and can be set between 0.5 and 10 seconds, with this function only active when the voltage exceeds 0.6 times the nominal voltage.
Technology Explained Simply
The relay monitors the applied voltage and responds when it falls below the set pickup value. In case of undervoltage, it switches the output contacts, which may trigger a warning signal or initiate a shutdown. Operational readiness is indicated by an LED display, which lights up when the operating voltage is present. A second LED indicates the active contact position. The device requires no auxiliary voltage and is thus independent of additional power supplies. The nominal power consumption values are 6 VA or 10 W. The temperature dependence of the measurement is < 0.05 % per Kelvin, ensuring stable operation even with temperature fluctuations.
Compatibility and Accessories
The relay is designed for use in enclosures and has a width of 45 mm, making it suitable for installation in standard switchboards. For variants with a DC voltage above 60 V, an external resistor is required, connected to terminals e and z. The measured voltage is connected to terminals e and f. The device complies with the standard IEC/EN 60255-1 and carries the certification mark CCC.
Mounting and Installation
Mounting is carried out in an enclosure, with the width of 45 mm determining the installation size. The terminals are clearly labeled, with terminals e, f, and z designated for voltage monitoring and the external resistor. When using an external resistor, sufficient shock protection and clearance from adjacent parts must be ensured, as the resistor becomes very hot during operation. The operating temperature of the device ranges from -20 °C to +60 °C.
Advantages in Operation
By enabling early detection of voltage anomalies, the relay allows for preventive maintenance and reduces the likelihood of machine downtime. The adjustable pickup and drop-out values, as well as the pickup delay, allow for application-specific customization. The LED indicators provide visual feedback on the operational status, speeding up fault localization. The high mechanical life of 30 million switching operations and the electrical life of 150,000 switching operations at 6 A and AC 230 V ensure long-term operation. The short-circuit resistance is protected by a maximum fuse rating of 4 A gG/gL.