Further information for Dold 0028732 BA9043/001 undervoltage relay 3AC50/60Hz 500V
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 500 V
Time delay
without
Approvals and Markings
UKCA
Variant
For 3p3w systems
The undervoltage relay BA9043/001 from Dold is a 3-phase monitoring device for three-phase power networks without a neutral conductor. It is designed for continuous monitoring of the network voltage and disconnects connected loads in case of undervoltage or voltage loss, preventing damage to electrical equipment. The device is rated for nominal voltages of 3AC 500 V and can be used in networks with frequencies from 50 to 400 Hz. Measurement is performed via arithmetic mean value measurement, where phases L1 and L2 are measured against L3, as no neutral conductor connection is available. Device settings are adjusted via rotary potentiometers on the front panel, enabling user-friendly and precise adjustment of the pickup and dropout values.
Applications
This relay is designed for use in industrial and railway applications, where reliable voltage monitoring is critical. It is particularly suitable for systems connected to three-phase networks without a neutral conductor, such as certain industrial machine controls or rail vehicles. The harmonic insensitivity ensures reliable operation even in networks with high harmonic loading.
Functions and Features in Detail
The device features 2 changeover contacts as output contacts, used for load protection and fault signal indication. The contacts are rated for a thermal current of up to 6 A per contact and meet switching capacities according to AC 15 (make: 2 A / AC 230 V) and DC 13 (break: 1 A / DC 24 V). The LED indicators show operational readiness (red LED) and activation of the output relay (green LED), enabling quick fault localization. The device operates on the zero-current principle, where the output relay is not activated in the event of a fault, ensuring safe disconnection.
Technical Explanation
The pickup value can be adjusted continuously between 0.85 and 1.05 of the nominal voltage, with the dropout value (hysteresis) adjustable between 0.75 and 0.95 of the pickup value. Time delay is not integrated in this variant, so the relay reacts immediately upon voltage drop. The maximum overload capacity is 1.2 times the nominal voltage continuously, allowing high tolerance for short-term voltage fluctuations.
Compatibility and Accessories
The relay is suitable for networks with frequencies from 50 to 400 Hz and complies with the standard IEC/EN 60255-1. It is designed for use in enclosures and is mounted on a DIN rail. The width is 45 mm, enabling compact installation in standard control panels. The UKCA certification confirms compliance with applicable safety and functional requirements.
Mounting and Installation
Mounting is done on a DIN rail according to IEC/EN 60715. The terminal connections are designed for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded conductors with heat-shrink tubing. Fixing is done using M3.5 plus-minus screws with self-locking clamp levers, with a torque of 0.8 Nm to be observed. Dimensions are 45 mm (width) × 73 mm (height) × 132 mm (depth).
Operational Advantages
Precise adjustability and LED indicators accelerate fault localization. Preventive maintenance is supported, as the device responds early to voltage anomalies. Harmonic insensitivity and stability under frequency fluctuations ensure reliable operation even under challenging network conditions. The device is designed for continuous operation and can be used at operating temperatures from -20 to +60 °C.
Approvals and Markings
The device carries the UKCA approval, confirming compliance with applicable European safety and functional requirements. Overvoltage category III and pollution degree 2 (rated impulse withstand voltage 6 kV) ensure high electrical safety.