Dold 0028667, EAN: 4030641286675

Dold 0028667 BA9036 AC50HZ 240V voltage relay

Dold 0028667 BA9036 AC50HZ 240V voltage relay

Lieske Part No. 1002189
Mfg Part No 0028667
EAN-Code 4030641286675
Manufacturer Dold
Here only 233,82 EUR
278,25 EUR incl. VAT

Further information for Dold 0028667 BA9036 AC50HZ 240V voltage relay

Technical data
1- / 3-phase1
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.AC 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9036
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltageAC 240 V 50 Hz
Time delaywithout
VariantUndervoltage relay. Closed circuit operation
The Dold voltage relay BA 9036 AC50HZ 240V is an undervoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks in industrial applications. It operates on the standby current principle, where the contact is closed in the normal state and opens in case of undervoltage or voltage loss. The device setting is adjusted via rotary switches on the front, ensuring simple and user-friendly configuration. The relay is designed for use in enclosures and has a width of 45 mm, making it suitable for standard control panels.

Applications
This relay is used in industrial plants to monitor voltage in electrical networks and trigger a response when deviations from preset values occur. It supports preventive maintenance and contributes to operational safety by detecting voltage drops early, which could otherwise lead to failures. Applications include systems with critical consumers, where an interrupted power supply could result in production downtime or damage.

Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or signaling systems. The pickup and drop-out values are adjustable and range from 0.85 to 1.05 times nominal voltage, with the variant /1_ _ offering a range of 0.9 to 1.25 times nominal voltage. The hysteresis is 0.75 to 0.95 of the set value, ensuring stable switching behavior during voltage fluctuations. The pickup delay is adjustable and ranges from 0.5 to 10 seconds, with this function only active when voltage exceeds 0.6 times nominal voltage. Operational readiness and contact position are indicated by LED displays – the upper LED lights up when operating voltage is present, and the lower LED indicates activation of the output relay.

Technology Explained Simply
The relay monitors the network voltage and reacts when it falls below the set threshold. In case of undervoltage, the contact opens, which can trigger a warning signal or initiate a motor shutdown. The nominal voltage is AC 240 V at 50 Hz, although the device is also available for other voltages in the range of AC 24 to 400 V. The maximum nominal voltage is AC 400 V. The device operates without auxiliary voltage, meaning it is directly connected to the network being monitored and does not require additional power supply. The nominal power consumption is 6 VA or 10 W. For DC voltages above 60 V, an external series resistor is required, connected to terminals e and z; the measured voltage is connected to e and f.

Compatibility and Accessories
The relay is designed for use in single-phase networks and complies with the standard IEC/EN 60255-1. It is rated for an operating temperature of -20 to +60 °C. The contact configuration with 2 changeover contacts allows control of multiple circuits. For DC applications above 60 V, external series resistors are required and are available in the accessories program (e.g. ZWS 20 SL 1.5 kΩ 20 W for DC 110 V). The switching capacity is up to 2 A at AC 230 V for closing contacts and 1 A for opening contacts, according to AC 15. For DC (DC 13), the switching capacity is 1 A at DC 24 V. The electrical life is 1.5 x 10⁵ switching operations at 6 A and AC 230 V, and the mechanical life is 30 x 10⁶ switching operations. Short-circuit resistance is ensured with a maximum fuse rating of 4 A gG / gL according to IEC/EN 60947-5-1.

Mounting and Installation
The relay is mounted in enclosures and is designed for installation in standard control panels. The connection terminals are clearly labeled; the measured voltage is connected to e and f, and the external series resistor (for DC >60 V) is connected to e and z. The LED displays allow visual monitoring of the operating status. Mounting is tool-free, and the 45 mm width facilitates placement in standard control panels.

Operational Advantages
Through early detection of voltage drops and the option of adjustable pickup delay, the relay can avoid unwanted shutdowns while ensuring timely response to critical voltage losses. The LED displays simplify diagnosis and maintenance. The design without auxiliary voltage reduces installation complexity and reduces the number of required supply lines. The high mechanical and electrical life ensures reliable long-term use in industrial environments.