Dold 0028371, EAN: 4030641283711

Dold 0028371 BA9041 3AC50HZ 415V phase sequence relay

Dold 0028371 BA9041 3AC50HZ 415V phase sequence relay

Lieske Part No. 1002061
Mfg Part No 0028371
EAN-Code 4030641283711
Manufacturer Dold
Here only 193,77 EUR
230,59 EUR incl. VAT

Further information for Dold 0028371 BA9041 3AC50HZ 415V phase sequence relay

Technical data
1- / 3-phase3
Enclosure designSwitch cabinet
Measuring range max.500 V
Output contacts2 C/O contacts
Standard measuring range3 AC 400 V
Width45 mm
TypeBA 9041
Variant
Contact equipping2 changeover contacts
Nominal voltage3AC 415 V 50 Hz
The phase sequence relay BA 9041 from Dold is a monitoring device for three-phase power networks, designed to monitor the correct phase sequence L1 - L2 - L3 and the presence of voltage in all three phases. It is particularly used to prevent incorrect rotation directions in electric drives, such as motors in production plants or conveyor systems. The device is designed for use in enclosures and is mounted on a DIN rail. It has a width of 45 mm, making it suitable for standard enclosure installations.

Applications
This relay is intended for industrial applications where correct phase sequence is critical for the safe operation of three-phase motors. It is used in systems where incorrect phase sequence could cause damage to the drive or operational disruptions. Monitoring is performed continuously, with the device checking voltage in all three phases. When the correct phase sequence is detected and voltage is present in all phases, the relay switches its output contacts to the active position, causing a green LED to illuminate. If the voltage in any phase drops below 60% of the rated voltage, the relay is de-energized and switches the contacts back to the default position.

Functions and Features in Detail
The device features two changeover contacts (11-12-14 and 21-22-24), which can be used to control auxiliary circuits or signal lamps. The operating time is less than 100 ms, and the reset time is less than 50 ms, enabling rapid response to voltage changes. The rated voltage is 3 AC 415 V at a frequency of 50 Hz, although the device is also suitable for voltages between 220 V and 500 V (in 20 V increments). The voltage range is between 0.8 and 1.1 times the rated voltage. The maximum measurable voltage is 500 V, with the standard measurement range set at 3 AC 400 V.

Technical Explanation
The phase sequence relay detects whether phases L1, L2, and L3 are present in the correct order. When the correct sequence is detected and sufficient voltage is present in all three phases, the relay is activated and switches its output contacts. A green LED indicates correct operation. In the event of a phase failure or incorrect phase sequence, the relay is de-energized, causing the contacts to return to their default position. The switching function is performed via two changeover contacts, which can be used to control auxiliary devices or alarms. The thermal current rating is 5 A, and the mechanical life expectancy is at least 50 million switching operations.

Compatibility and Accessories
The relay is designed for use in three-phase AC networks and complies with the standard IEC/EN 60255-1. It is designed for an operating temperature range of -20 °C to +60 °C and can be operated up to an altitude of 2000 m above sea level. The enclosure protection rating is IP 40, providing protection against contact with tools and against splashing water from all directions. The terminals are protected to IP 20. In networks with high harmonic content, such as those found in thyristor systems or reactive power compensation systems, the device may produce incorrect results. In such cases, it is recommended to test a sample device on-site. For detecting voltage asymmetries not caused by phase sequence errors, the asymmetry relay BA 9040 is recommended.

Mounting and Installation
The device is mounted on a DIN rail inside an enclosure. The connection terminals are designed for solid conductors up to 2.5 mm² or stranded conductors up to 1.5 mm². Dimensions are 45 mm (width) × 73.2 mm (height) × 119.8 mm (depth). Mounting is achieved using a flat terminal with a self-lifting clamp, requiring a torque of 0.8 Nm. The cable cover depth is 10 mm. Installation must take place in a closed enclosure, with ambient temperature within the specified operating range.

Operational Advantages
Using the BA 9041 ensures correct rotation direction of drives, thereby preventing damage to motors or mechanical components. The simple wiring and clear indication via the green LED simplify commissioning and maintenance. The device is designed for continuous operation and consumes less than 3.5 VA. Its high mechanical life and robust construction ensure reliable performance over a long period. Compliance with the standard IEC/EN 60255-1 guarantees the quality and safety of the device.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002061
qrcode für Dold 0028371 BA9041 3AC50HZ 415V phase sequence relay