Further information for Dold 0028125 BA9043/001 undervoltage relay 415V
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 415 V
Time delay
without
Approvals and Markings
UKCA
Variant
For 3p3w systems
The Dold undervoltage relay BA9043/001 is a 3-phase monitoring device for three-phase networks without a neutral conductor. It is designed for continuous monitoring of the supply voltage and responds to undervoltage by switching the output contacts. The device is rated for nominal voltages of 3AC 415 V and complies with the standard IEC/EN 60255-1. Measurement is performed via arithmetic mean of the three phases, with this variant measuring L1 and L2 against L3. The setting of pickup and dropout values is done via rotary potentiometers on the front of the device, allowing user-friendly adjustment to the specific application.
Applications
This relay is designed for use in industrial and railway applications where reliable voltage monitoring is required. It is particularly suitable for networks with frequencies between 50 and 400 Hz. The device is intended for installation in enclosures, with a width of 45 mm enabling compact mounting on a DIN rail. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which change state in the event of undervoltage. The pickup delay is active, but in this variant, no adjustable time delay is available. The output relays operate on the rest current principle, meaning they are not activated in the event of a fault. Operating readiness and contact position are indicated by LED displays: a red LED indicates that supply voltage is present, and a green LED indicates activation of the output relay. The device is insensitive to harmonics, ensuring stable operation even with distorted voltage waveforms.
Technology Explained Simply
Voltage measurement is performed by arithmetic mean of the three phases. In the BA9043/001 variant, designed for networks without a neutral conductor, phases L1 and L2 are measured against L3. The pickup value can be set continuously between 0.85 and 1.05 times the nominal voltage, and the dropout value (hysteresis) is between 0.75 and 0.95 of the pickup value. The maximum overload capacity is 1.2 times the nominal voltage continuously. The nominal power consumption is 4 VA. Switching delay is not available in this variant, although other variants offer an adjustable time delay of 0.5 to 10 seconds.
Compatibility and Accessories
The relay is designed for 3-phase networks without a neutral conductor and can be used in systems with frequencies from 50 to 400 Hz. It has a width of 45 mm for mounting on DIN rails. The terminals are rated for 2 x 2.5 mm² solid or 2 x 1.5 mm² flexible conductors with cable glands. Mounting is done using plus-minus terminal screws M3.5 with self-lifting terminals. The maximum operating altitude is 2000 m above sea level.
Mounting and Installation
Mounting is on a DIN rail according to IEC/EN 60715. The connection terminals are designed for solid or flexible conductors, with a stripping length of 10 mm. The tightening torque for the terminals is 0.8 Nm. The terminal markings are L1, L2, L3 for the supply connections and 11, 12, 14 as well as 21, 22, 24 for the two changeover contacts. The front of the device features two rotary potentiometers for setting the pickup and dropout values.
Operational Advantages
The use of this relay enables preventive maintenance, as early voltage drops can be detected and documented. Rapid fault localization via LED indicators and clear signaling of contact position support operational management. Insensitivity to harmonics ensures reliable operation even in networks with high harmonic loading. The adjustability of pickup and dropout values allows adaptation to specific requirements of the respective installation. Operational safety is ensured by short-circuit resistance and a maximum fuse rating of 4 A gG/gL. The mechanical life exceeds 30 million switching operations, and the electrical life at 3 A and AC 230 V is 200,000 switching operations.
Approvals and Markings
The device carries the UKCA mark, confirming compliance with applicable European safety and operational requirements. EMC requirements according to IEC/EN 61000-4-2 to -4-5 are met, with static discharge (ESD) up to 8 kV (air discharge), HF radiation up to 20 V/m, and fast transients up to 2 kV permitted. The overvoltage category is III, and the rated impulse voltage is 6 kV at pollution degree 2.
Switching Capacity and Lifespan
The switching capacity according to AC 15 is 2 A at AC 230 V for closing contacts, 3 A at 0.1 Hz, and 1 A for opening contacts. According to DC 13, it is 1 A at DC 24 V. The electrical life at 3 A and AC 230 V (cos φ = 1) is 200,000 switching operations, and the mechanical life is over 30 million switching operations. The thermal current rating (Ith) is up to 6 A per contact.
Operating Conditions
The device is designed for continuous operation. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level. The creepage and clearance distances correspond to a rated impulse voltage of 6 kV at pollution degree 2 according to IEC 60664-1.
Connection and Wiring
The connection terminals are rated for 2 x 2.5 mm² solid or 2 x 1.5 mm² flexible conductors with cable glands. Mounting is done using plus-minus terminal screws M3.5 with self-lifting terminals. The stripping length is 10 mm, and the tightening torque is 0.8 Nm. The terminal markings are L1, L2, L3 for the supply connections and 11, 12, 14 as well as 21, 22, 24 for the two changeover contacts.