Further information for Dold 0027750 BA9043 3/N undervoltage relay
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3/N 240/415 V
Time delay
without
Approvals and Markings
UKCA
Variant
For 3p4w systems
The undervoltage relay BA 9043 from Dold is a 3-phase monitoring device for three-phase networks with neutral conductor. It is designed for continuous monitoring of the network voltage and responds to undervoltage by switching the output contacts. The device is rated for nominal voltages of 3/N AC 240/415 V and can be used in networks with frequencies from 50 to 400 Hz. Measurement is performed by arithmetic mean calculation of the three phases against the neutral conductor, ensuring precise voltage monitoring. Device settings are adjusted via rotary potentiometers on the front panel, allowing the pickup and dropout values to be continuously adjusted between 0.85 and 1.05 of the nominal voltage, with a hysteresis of 0.75 to 0.95 of the pickup value.
Applications
This relay is designed for use in industrial and railway applications where reliable voltage monitoring is required. It is particularly suitable for installations that depend on stable network voltage to prevent failures or damage to machines and equipment. The device is installed in enclosures and has a width of 45 mm, allowing integration into standard DIN rail mounting.
Functions and Features in Detail
The BA 9043 features two changeover contacts as output contacts, which change state in case of undervoltage. The device operates on the rest current principle, meaning the output relay is not activated in the event of a fault. Operational readiness and contact status are indicated by LED displays: a red LED lights up when operating voltage is present, and a green LED indicates activation of the output relay. The devices are insensitive to harmonics, meaning they operate reliably even in networks with harmonic distortions.
Technology Explained Simply
Voltage monitoring is performed by measuring each phase against the neutral conductor. Arithmetic mean calculation ensures that even with uneven voltage conditions in individual phases, the overall voltage is correctly determined. In this variant, the pickup delay is not activated; however, the function is available in other variants (e.g. BA 9043/002) with an adjustable time delay of 0.5 to 10 seconds. Below 0.4 times the nominal voltage, the relay drops out immediately, while the time delay is active for voltages between 0.4 and 0.6 times the nominal voltage.
Compatibility and Accessories
The relay is designed for three-phase networks with neutral conductor and complies with standards IEC/EN 60255-1. It is suitable for operation at altitudes up to 2000 m above sea level and can be operated in environments with temperatures from -20 to +60 °C. The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V, while the mechanical life expectancy exceeds 30 million switching operations. Switching capacities are 2 A/AC 230 V for closing contacts and 1 A/AC 230 V for opening contacts according to AC 15 (IEC/EN 60947-5-1). Maximum short-circuit withstand requires a fuse of max. 4 A gG/gL.
Mounting and Installation
Mounting is done on DIN rails in accordance with IEC/EN 60715. The connection terminals are designed for 2 x 2.5 mm² single- or multi-strand conductors, with a stripping length of 10 mm. Fixing is done using M3.5 plus-minus screws with a self-locking clamp lever. Tool-free mounting is possible, as the screws are tightened to a torque of 0.8 Nm. Terminal markings include connections L1, L2, L3, N for the network to be monitored, as well as contacts 11, 12, 14 and 21, 22, 24 for the output relays.
Operational Advantages
The BA 9043 enables preventive maintenance through early detection of voltage drops. Rapid fault localization reduces downtime and increases productivity. Simple operation via rotary potentiometers and clear LED indication facilitate commissioning and maintenance. The device is designed for continuous operation and features high mechanical and electrical life expectancy, ensuring operational safety in critical installations. EMC coverage includes immunity to electrostatic discharge (8 kV), high-frequency radiation (20 V/m), fast transients (2 kV), and surge voltages (1 kV between conductors, 2 kV between conductors and earth).