Further information for Dold 0027159 BA9043/003 undervoltage relay 380V
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Switch cabinet
Nominal voltage max.
3/N AC 690 / 400 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9043
Operate delay
Variant
Contact equipping
2 changeover contacts
Nominal voltage
3AC 380 V
Time delay
0,5 - 10 s
Approvals and Markings
UKCA
Variant
For 3p3w systems. With adjustable time delay
The Dold undervoltage relay BA9043/003 is a 3-phase monitoring device for three-phase networks without a neutral conductor. It is designed for continuous monitoring of the supply voltage and de-energizes output contacts in case of undervoltage, protecting connected devices from damage. The device is rated for nominal voltages of 3AC 380 V and operates within a frequency range of 50 to 400 Hz. Measurement is performed via arithmetic mean value calculation, with phases L1 and L2 measured against L3, as no neutral conductor connection is available. The setpoints for pickup and dropout values are continuously adjustable via rotary potentiometers on the device front, enabling user-friendly adaptation to specific applications.
Applications
This relay is suitable for industrial applications as well as railway installations where reliable voltage monitoring is required. It is mounted in enclosures and designed for continuous operation. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The maximum operating altitude is 2000 m above sea level. The devices are specified according to IEC/EN 60255-1 and carry the UKCA mark.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, rated for switching operations with a thermal current of up to 6 A per contact. Switching capacities are 2 A/AC 230 V for closing contacts and 1 A/AC 230 V for opening contacts according to AC 15, as well as 1 A/DC 24 V according to DC 13. The electrical life expectancy is at least 200,000 switching operations at 3 A and AC 230 V. The mechanical life expectancy exceeds 30 million switching operations. The contacts are equipped with LED indicators for operational readiness (red LED) and contact position (green LED), enabling visual inspection of the operating status.
Technology Explained Simply
The pickup delay is activated, meaning the device does not react immediately to voltage dips but incorporates a short delay to filter out brief fluctuations. The time delay is adjustable between 0.5 and 10 seconds and only applies when the voltage is at least 60 % of the nominal voltage. Below 40 % of the nominal voltage, the output relay drops out immediately. The rest current principle ensures that the output relay is not activated in the event of a fault, increasing safety. The device is insensitive to harmonics, making it suitable for networks with high harmonic loading.
Compatibility and Accessories
The relay is designed for networks with or without a neutral conductor, with variant BA9043/003 specifically intended for systems without a neutral conductor. It is available for nominal voltages from 3/N AC 100/57 V to 690/400 V, with the specified variant being 3AC 380 V. The maximum overload capacity is 1.2 times the nominal voltage continuously. The nominal power consumption is 4 VA. The devices are designed for frequencies from 50 to 400 Hz, with a frequency tolerance of ±5 %.
Mounting and Installation
The device is mounted on a DIN rail (IEC/EN 60715). The terminal connections are designed for 2 x 2.5 mm² solid or 2 x 1.5 mm² stranded conductors with heat-shrink tubing. Dimensions are 45 mm (width) x 73 mm (height) x 132 mm (depth). The terminal fastening is achieved using M3.5 plus-minus screws with self-locking function. Connections are made according to DIN 46228-1/-2/-3/-4. The stripping length is 10 mm, and the tightening torque is 0.8 Nm.
Advantages in Operation
The continuous adjustability of pickup and dropout values allows precise adaptation to specific applications. The LED indicators facilitate fault localization and preventive maintenance. Harmonic insensitivity ensures reliable operation even in networks with high harmonic loading. The time delay reduces false tripping due to brief voltage dips. The enclosure-compatible design and DIN rail mounting enable easy integration into existing systems. The maximum operating altitude of 2000 m and temperature range from -20 °C to +60 °C make the device suitable for a wide range of operating conditions.