Technical data
ClassificationThermistor-Motorschutz
Enclosure designSwitch cabinet
Measuring range max.> 3 kΩ
Output contacts1 C/O contact, 2 C/O contacts
Width45 mm
TypeBA 9038
Variant
Auxiliary voltageAC 230 V
Contact equipping1 changeover contact
VariantWithout thermal reclosing interlock (manual reset function)
The Thermistor motor protection relay BA9038 by Dold, type BA9038.11AC50/60HZ230V, is an enclosure device for temperature monitoring of electric motors and other thermally loadable components such as bearings, gearboxes, oils or coolants. It serves to prevent thermal overloads that may occur due to high switching frequency, heavy start-up, single-phase operation, impaired cooling or high ambient temperature. The device operates on the standby current principle, whereby the output relay does not activate in the event of a fault, but drops out, enabling safe disconnection of the motor.

Applications
This motor protection relay is designed for use in industrial plants where reliable temperature monitoring of electrical machines is required. It can be mounted in enclosures and is particularly suitable for applications where thermal overload must be prevented due to mechanical or electrical disturbances. Monitoring is performed via thermistors (PTC resistors) integrated into the motor windings. Up to six such thermistors can be connected in series, enabling flexible adaptation to different motor sizes and configurations.

Functions and equipment in detail
The device features an input for thermistors or bimetal contacts and detects a wire break in the sensor circuit to avoid false alarms caused by defective sensors. The tripping condition is triggered by a resistance value of at least 3 kΩ, with the reset value being at most 1.8 kΩ. The response delay is maximum 20 ms, and the reset delay is maximum 15 ms. The auxiliary voltage is AC 230 V, and the device width is 45 mm, making it suitable for standard control panels.

Technology explained simply
The relay operates on the standby current principle, where the circuit is closed during normal operation. When the motor temperature rises and the resistance of the thermistors reaches the response threshold of ≥ 3 kΩ, the output relay drops out. This leads to disconnection of the motor to prevent overheating. The reset delay ensures that the relay does not immediately re-engage when the temperature drops, but only after a short delay. The wire break detection monitors the sensor circuit and prevents faulty sensors from causing malfunction.

Compatibility and accessories
The device is designed for use with specific PTC thermistors integrated into the motor windings. The connecting wires from the thermistor to terminals P1 and P2 must not be influenced by external voltages and should be routed in a separate cable. The total resistance of the wiring should be ≤ 100 Ω. The BA9038.11AC50/60HZ230V version features 1 changeover contact as output contact. Variants with 2 changeover contacts are available, but this is not the configuration of this item. The devices comply with the standard IEC/EN 60947-8.

Mounting and installation
The motor protection relay is mounted in enclosures. Terminal designations are: A1/A2 for auxiliary voltage, P1/P2 for measurement input, 11/12/14 for contacts of the first relay, and 21/22/24 for contacts of the second relay (in 2-changeover configuration). Installation is carried out according to the requirements of standard IEC/EN 60947-8.

Advantages in operation
The BA9038 provides reliable and precise temperature monitoring, extending motor life and reducing downtime. The wire break detection increases safety by preventing malfunction due to a defective sensor. The voltage-free re-energizing lockout is not included in this version, meaning the device must be manually reset after tripping. The width of 45 mm allows compact mounting in standard control panels. The auxiliary voltage of AC 230 V is common in many industrial plants and ensures stable power supply.
This is an offer of: