Dold 0026357, EAN: 4030641263577

Dold 0026357 undervoltage relay 220/380V 0.5-10s

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0026357 undervoltage relay 220/380V 0.5-10s

Lieske Part No. 992796
Mfg Part No 0026357
EAN-Code 4030641263577
Manufacturer Dold
Here only 302,01 EUR
359,39 EUR incl. VAT

Further information for Dold 0026357 undervoltage relay 220/380V 0.5-10s

Technical data
1- / 3-phase3
Auxiliary voltageWithout
Enclosure designSwitch cabinet
Nominal voltage max.3/N AC 690 / 400 V
Output contacts2 C/O contacts
Width45 mm
TypeBA 9043
Operate delayYes
Variant
Contact equipping2 changeover contacts
Nominal voltage3/N 220/380 V
Time delay0,5 - 10 s
Approvals and MarkingsUKCA
VariantFor 3p4w systems. With adjustable time delay
The undervoltage relay BA9043/0023AC50/60HZ220/380V10S from Dold is a 3-phase monitoring device for AC networks with neutral conductor. It is designed for continuous monitoring of network voltage and disconnects connected loads in case of undervoltage or voltage loss to prevent damage to electrical devices. The device is rated for nominal voltages of 3/N AC 220/380 V and can be used in networks with frequencies from 50 to 400 Hz. Measurement is performed by arithmetic mean calculation of the three phases against the neutral conductor, ensuring precise and reliable voltage monitoring. The setting of pickup and dropout values is done via rotary potentiometers on the device front, enabling user-friendly and stepless adjustment.

Applications
This relay is suitable for industrial applications as well as railway applications. It monitors 3-phase AC networks and is specifically designed for systems requiring high availability. Installation is carried out in enclosures, with a width of 45 mm allowing compact mounting on a DIN rail.

Functions and Equipment in Detail
The device features two changeover contacts, which can be used for controlling auxiliary functions or disconnecting loads. The contact rating is up to 6 A per contact for thermal current. The switching delay is adjustable and ranges from 0.5 to 10 seconds. This time delay is only effective if the network voltage is at least 60 % of the nominal voltage. Below 40 % of the nominal voltage, disconnection occurs immediately. The pickup delay is activated, meaning the device has a short delay when responding to ensure filtering of short-term voltage fluctuations.

Technology Explained Simply
Voltage monitoring is achieved by measuring each phase against the neutral conductor and then calculating the arithmetic mean. This ensures an accurate representation of the actual voltage condition in the network. LED indicators on the front panel signal operational readiness (red LED) and activation of the output relay (green LED). The zero-current principle ensures that the output relay is not activated in case of fault, increasing safety. The device is insensitive to harmonics, meaning it operates reliably even with network voltages containing high harmonic content.

Compatibility and Accessories
The relay is available for networks with or without neutral conductor, with the variant described here specifically designed for systems with neutral conductor. The nominal voltage range extends from 3/N AC 100/57 V to 690/400 V, with the specified version designed for 220/380 V. The frequency range of 50 to 400 Hz makes the device suitable for a wide variety of applications. Compliance with the standard IEC/EN 60255-1 ensures conformity with international standards for measuring instruments.

Mounting and Installation
Mounting is done on a DIN rail inside the enclosure. The connection terminals are rated for cable cross-sections of 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded). Cables are secured using M3.5 plus-minus screws with self-lifting clips. Dimensions are 45 mm (width) x 73 mm (height) x 132 mm (depth). The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +60 °C. The operating altitude is limited to a maximum of 2000 m above sea level.

Advantages in Operation
The stepless adjustability of pickup and dropout values allows precise adaptation to specific requirements. The LED indicators facilitate diagnosis and fault localization. The ability to operate without auxiliary voltage reduces installation complexity. The time delay prevents unnecessary disconnections during short-term voltage dips. The high mechanical life of over 30 million switching operations and the electrical life of 200,000 switching operations at 3 A and AC 230 V ensure long service life. Compliance with the standard IEC/EN 60255-1 and UKCA approval guarantee the quality and safety of the device.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/992796
qrcode für Dold 0026357 undervoltage relay 220/380V 0.5-10s