| Technical data |
| Enclosure design | Front panel mounting |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 72 mm |
| Type | EF 7666 |
| Variant |
| Contact equipping | 1 changeover contact delayed, 1 changeover undelayed |
| Nominal voltage | AC 230 V |
| Time range | 0,15 - 1000 s |
The Dold time relay EF7666.32 is a drop-out delayed industrial time relay for front panel mounting, designed for a rated voltage of AC 230 V and a frequency of 50/60 Hz. It is used for time-delayed control of electrical loads, particularly in applications where a controlled shutdown process is required, such as motor coast-down or the shutdown of heating and cooling systems. The function is based on a purely mechanical time delay, which is adjusted via a continuous rotary switch on the front side. The time delay can be set within a range of 0.15 to 1000 seconds, with six switchable time ranges available, which can be adjusted continuously via an adjustment pointer on an absolute scale. The repeatability is ≤ ± 0.5 % of the scale end value, with a deviation of ≤ ± 1 % allowed in the 3 and 6 second ranges.
Applications
This device is designed for industrial control tasks where precise, time-delayed shutdown is required. Typical applications include the control of drives, fans, pumps, or lighting systems, where immediate shutdown is not desired. The drop-out delay allows the load to continue operating for a defined period after the control signal is switched off. The zero-voltage safety ensures that the relay safely returns to its default position in the event of a voltage drop or failure.
Functions and Equipment in Detail
The time relay features two output contacts: one changeover contact that switches with delay, and one changeover contact that switches without delay. The delayed contacts switch only after the set delay time has elapsed, while the non-delayed contacts respond immediately when the control signal is applied. This contact configuration enables flexible switching arrangements in control systems. The contact materials consist of AgNi with a gold layer of 0.2 μm, ensuring high switching durability and corrosion resistance. The operating time of the contacts is less than 35 ms, and the drop-out time is less than 60 ms.
Technology Explained Simply
The time delay is purely mechanical, without electronic components, which increases reliability and robustness. The delay time is adjusted via a continuous rotary switch on the front side, equipped with an absolute scale and an adjustment pointer. The reset time is less than 150 ms, meaning the device is quickly ready for the next operation after the last switching cycle. The time delay indicator allows visual monitoring of the current state of the time delay. The front side of the device is protected against spray water and complies with protection class IP 65, enabling use in outdoor or humid environments.
Compatibility and Accessories
The device is designed for use in industrial control systems and can be combined with other devices from the MINITIMER series, such as models AA 7666, EC 7666, and EH 7666. The contact rating is designed for a nominal operating voltage of AC 250 V. The switching capacity according to AC 15 is 3 A at AC 230 V. The electrical life expectancy is 1 x 10⁵ switching operations at 3 A and 5 x 10⁵ switching operations at 1 A. The mechanical life expectancy exceeds 30 x 10⁶ switching operations or 15000 operating hours.
Mounting and Installation
The device is designed for front panel mounting and has a mounting width of 72 mm. The front surface measures 72 x 72 mm. Mounting is carried out on a suitable control panel, with connection terminals provided for connecting control and load lines. Connection designations are detailed in the data sheet. Installation must follow the manufacturer’s technical specifications, with a maximum fuse rating of 10 A gG / gL.
Operational Advantages
The combination of wide adjustment range, high repeatability, and mechanical reliability makes this device a robust solution for industrial control tasks. Front-side adjustment allows for easy and quick modification of the delay time during operation. The IP 65 protection class ensures safe use in humid or dusty environments. Zero-voltage safety ensures safe reset in case of failure. The switching position indicator (except for EH 7666) enables visual monitoring of the switching state.