| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts max. | 4 NC contacts, 4 NO contacts |
| Thermal current Ith max. | 8 A |
| Width | 45 mm |
| Type | AD 8851 |
| Variant |
| Contact equipping | 4 changeover contacts |
| Nominal voltage | DC 220 V |
The Dold toggle relay AD8851.14 DC220V is a bistable relay for use in enclosures, featuring a contact configuration with 4 changeover contacts. It is designed for a nominal voltage of DC 220 V and is suitable for locking control circuits in industrial applications where a secure and mechanically robust switching function is required. The device operates according to the standard IEC/EN 61810-1 and features a solid, torsion-resistant mounting construction that supports both flap armature magnetic systems and the common contact block. This ensures the relay remains stable and reliable even under high mechanical loads.
Applications
This toggle relay is used in industrial control and protection systems, particularly where a bistable switching function is needed, meaning a position that is maintained after de-energization. Typical application areas include machine controls, plant automation, and safety circuits, where the contact position must be clearly visible even when de-energized. The width of 45 mm allows for compact mounting in standard enclosures.
Functions and Equipment in Detail
The bistable function is achieved through two flap armature magnetic systems that interlock with each other. The switching position remains unchanged even after de-energization. Operation is performed via pulse or continuous energization of coils A1-A2 or B1-B2. A manually operated toggle lever mounted on the front plate allows manual adjustment of the magnetic system and simultaneously indicates the current magnetic and contact position. This is particularly useful for maintenance, diagnostics, and manual override.
Technology Explained Simply
The contacts are arranged on a common magnetic system connected to coil A1-A2. This ensures that no undefined contact states occur when both systems are energized simultaneously. The contact configuration includes 4 changeover contacts, equivalent to a maximum of 4 normally open and 4 normally closed contacts. The thermal current Ith is up to 8 A, applicable when using two contacts. When using three contacts, the thermal current is 5 A; with four contacts, it is 4 A. The response and release time of the contacts is each under 40 ms, ensuring fast switching response.
Compatibility and Accessories
The relay is designed for a nominal voltage of DC 220 V, with an operating voltage range between 0.8 and 1.1 times the nominal voltage. It is designed for continuous operation and can be operated in a temperature range from -20 °C to +45 °C. The maximum switching frequency is 3000 switching operations per hour. The electrical life is 1 x 10⁵ switching operations at 1 A and AC 230 V, with 3000 switching operations per hour possible at 50 % switching capacity. The mechanical life is 50 x 10⁶ switching operations. Short-circuit resistance is ensured by a maximum fuse rating of 10 A gG/gL according to IEC/EN 60947-5-1.
Mounting and Installation
The relay is mounted in enclosures and is designed for installation in standard plug-in strips. The width of 45 mm corresponds to the standard for enclosure components. The connection terminals are clearly labeled, with coils A1-A2 and B1-B2 designated for control. The contacts are configured as changeover contacts (11-12-14, 21-22-24, 31-32-34, 41-42-44). The switching diagrams in the datasheet show the assignment of contacts to the coils, with the coil marked with an asterisk closing the corresponding contacts.
Advantages in Operation
The toggle relay offers high mechanical stability and reliability, even under harsh operating conditions. Manual operation via the toggle lever enables easy maintenance and diagnostics. The clear indication of contact position increases transparency during operation. The high mechanical life of 50 million switching operations and the electrical life of 100,000 switching operations at 1 A and AC 230 V make the device suitable for long-term applications. Compliance with the standard IEC/EN 61810-1 ensures standardized quality and interoperability in industrial installations.
Approvals and Markings
The device complies with the requirements of standard IEC/EN 61810-1. The electrical life is evaluated according to IEC/EN 60947-5-1. Switching capacity for make contacts (3 A / AC 230 V) and break contacts (1 A / AC 230 V) is defined according to AC 15. The permissible altitude is up to 2000 m above sea level. Insulation values are 4 kV at pollution degree 2 according to IEC 60664-1. EMC requirements include immunity to electrostatic discharge (6 kV), high-frequency radiation (10 V/m in the range 80 MHz to 6 GHz), fast transients (4 kV), and overvoltages between conductors (2 kV).