Further information for Dold 0022746 time relay delayed 230 V
General
Device type
BA 7905
Time function
Delayed operation
Time range
0,05 s
Output contacts
2 change-over contacts
Mounting width
45 mm
Nominal voltage
AC, DC
Repeatability
< ± 1 %
DC voltage without resistor
up to 220 V
LED indicators
Ready for operation and contact position
Norm
EN 61812-1
Remote potentiometer connection
Technical data
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Time function(s)
On-delay
Width
45 mm
Type
BA 7905
Variant
Contact equipping
2 changeover contacts delayed
Nominal voltage
AC 230 V
Time range
0,05 - 1 s
The time relay BA 7905 from Dold is a delayed-activation control device designed for use in enclosures. It enables time-delayed activation of electrical devices and controls, with the delay time being continuously adjustable between 0.05 seconds and 300 seconds. This function allows for controlled motor start-up or sequential switching of system components, helping to avoid mechanical stress or current surges. Adjustment is made via a rotary switch that covers a wide range, enabling flexible adaptation to various applications.
Applications
This device is designed for industrial control and switching systems, particularly in installations where precise timing of switching operations is required. Typical applications include controlling pumps, fans, motors, or lighting systems, where immediate switching is either undesirable or technically impractical. The delayed-activation function ensures that the relay only switches the output contact after the set delay time has elapsed, enhancing operational safety.
Functions and Features in Detail
The time relay features 2 changeover contacts as output contacts, suitable for controlling loads within enclosures. The repeatability accuracy is less than ±1%, ensuring high precision in repeated switching operations. The operating voltage can be either alternating current (AC) or direct current (DC), with no additional series resistor required for DC voltages up to 220 V. The delay time is adjusted via a continuously variable rotary switch, allowing for easy and precise adjustment.
Technology Explained Simply Delayed activation means that the relay does not respond immediately when input voltage is applied, but only after the set time has elapsed. This is especially useful for switching loads in a specific time sequence. The switching function is performed by two changeover contacts, each providing a switching contact for the closed and open states. The LED indicators signal operational readiness and the current contact position, simplifying diagnostics and maintenance. The remote potentiometer connection allows external adjustment of the delay time, which is advantageous in complex systems.
Compatibility and Accessories
The device is designed for use in enclosures and complies with the standard EN 61812-1. It includes a remote potentiometer connection, enabling integration with external adjustment devices. No series resistors are required for DC voltages up to 220 V, simplifying installation. There are no specific accessories listed that can be directly combined with this model.
Mounting and Installation
The time relay has a width of 45 mm, making it suitable for standard enclosure mounting. It is inserted into the enclosure and connected with the appropriate cables. Mounting typically occurs within an enclosure, with electrical connections made according to the wiring diagram. The LED indicators facilitate visual inspection of operational states during installation.
Operational Advantages
The high repeatability accuracy ensures consistent switching operations, increasing system reliability. The wide adjustment range from 0.05 to 300 seconds offers flexibility for adapting to different applications. The simple adjustment via the rotary switch reduces installation time. The LED indicators support maintenance by allowing visual verification of the operational status. The delayed-activation function enhances safety, especially in systems with mechanical loads that must not be subjected to immediate stress.
Scope of Delivery
The delivery includes the time relay BA 7905 with integrated LED indicators and remote potentiometer connection. No additional components such as batteries or extra cables are included.